| Plan Review Notes For Permit 18050588 |
| Permit Number |
18050588 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-07-14 12:19:30 | ****CORRECTIONS**** | | | W.P.B. PERMIT: 18050588 (2ND REVIEW) | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. OK | | | | | | 2. OK | | | | | | 3. COMMENT NOT ADDRESSED. | | | PROVIDE SOILS REPORT. | | | FBC 1803.1 GENERAL.GEOTECHNICAL INVESTIGATIONS SHALL BE | | | CONDUCTED IN ACCORDANCE WITH SECTION 1803.2 AND | | | REPORTED IN ACCORDANCE WITH SECTION 1803.6. WHERE | | | REQUIRED BY THE BUILDING OFFICIAL OR WHERE GEOTECHNICAL | | | INVESTIGATIONS INVOLVE IN-SITU TESTING, LABORATORY | | | TESTING OR ENGINEERING CALCULATIONS, SUCH | | | INVESTIGATIONS SHALL BE CONDUCTED BY A REGISTERED | | | DESIGN PROFESSIONAL. | | | | | | 4. OK | | | | | | 5. OK | | | | | | 6. NEW COMMENT DUE TO ADJUSTED ELEVATION NAV88. | | | [FBC R322.2.2]ENCLOSED AREA BELOW DESIGN FLOOD | | | ELEVATION (GARAGE). FOLLOW R322.2.2.1 FOR INSTALLATION | | | HEIGHTS OF FLOOD VENTS. | | | | | | NOTE:IF OPEN WEB TYPE FLOOR JOISTS ARE BEING USED THEN | | | SMOKE COMPARTMENTS WILL BE NEEDED [FBC R302.12]. | | | | | | THIS PERMIT WILL BE ISSUED WITH PROVISO: | | | BUILDING UNDER CONSTRUCTION ELEVATION CERTIFICATE IS | | | REQUIRED PRIOR TO CONCRETE POUR | | | FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS REQUIRED | | | PRIOR TO CO |
|