| 2018-06-07 15:57:45 | 06/07/2018 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. A SEPARATE PERMIT SHALL BE REQUIRED FOR IRRIGATION |
| | SYSTEM AND A BACKFLOW DEVICE, THE POTABLE WATER SUPPLY |
| | TO LAWN IRRIGATION SYSTEMS SHALL BE PROTECTED AGAINST |
| | BACKFLOW BY AN ATMOSPHERIC VACUUM BREAKER, A PRESSURE |
| | VACUUM BREAKER ASSEMBLY OR A REDUCED PRESSURE PRINCIPLE |
| | BACKFLOW PREVENTION ASSEMBLY. VALVES SHALL NOT BE |
| | INSTALLED DOWNSTREAM FROM AN ATMOSPHERIC VACUUM |
| | BREAKER. WHERE CHEMICALS ARE INTRODUCED INTO THE |
| | SYSTEM, THE POTABLE WATER SUPPLY SHALL BE PROTECTED |
| | AGAINST BACKFLOW BY A REDUCED PRESSURE PRINCIPLE |
| | BACKFLOW PREVENTION ASSEMBLY. 2017 FBC R2902.5.3 LAWN |
| | IRRIGATION SYSTEMS. |
| | |
| | 2. POWER BATH WATER CLOSET NEEDS TO BE VENTED BY LAB |
| | WHICH IS ON TRUNK LINE. 2017 FBC R3101.2.1 VENTING |
| | REQUIRED. |
| | |
| | 3. THE 4? PVC GOING TO SECOND FLOOR IS NOT REQUIRED PER |
| | CODE AND MAY BE TOO LARGE TO RUN IN TRUSSES. THE CODE |
| | WILL ALLOW A 3? PIPE BE USED PLEASE REFER TO P3004.1 |
| | DWV SYSTEM LOAD. |
| | |
| | 4. WATER HEATER PAN TERMINATION ON DRAIN PAN SHALL |
| | TERMINATE OUTSIDE BUILDING AND RELIEF SHALL TERMINATE |
| | IN PAN ON PAGE P001, 2017 FBC R 2801.6.2 |
| | |
| | 5. BACKFLOW PREVENTER DEVICE SHALL BE MIN 5? FROM METER |
| | PER UTILITIES DEPARTMENT AND PLEASE VISIT CITY OF WEST |
| | PALM BEACH UTILITY DEPARTMENT. YOU CAN REFER TO THEIR |
| | CROSS CONNECTION MANUAL IN THE CITY WEB SITE HTTP://WPB |
| | .ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLICATIONS/BA |
| | CKFLOW-CROSS-CONNECTION-CONTROL-MANUAL FOR MORE |
| | INFORMATION. |
| | |
| | 6. ROMAN TUB STANDALONE REQUIRED A CONTROL VALVE BY A |
| | WATER TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| | 1070 OR CSA B125.3, EXCEPT WHERE SUCH PROTECTION IS |
| | OTHERWISE PROVIDED BY A COMBINATION TUB/SHOWER VALVE IN |
| | ACCORDANCE WITH SECTION P2708.4. FBC R 2713.3 BATHTUB |
| | AND WHIRLPOOL BATHTUB VALVES. THIS VALVE IF REQUIRED |
| | HAS TO BE ACCESSIBLE LOCATION LIKE UNDER A CABINET OR A |
| | WALL PANEL. |
| | |
| | 7. WATER HEATER EF 0.92 ON A 50 GALLON OF FORM |
| | R405-2017 IS NOT CORRECT ACCORDING TO NEACA HOT WATER |
| | REGULATION 2015 AND IT SHOULD BE AT EF 0.95, PLEASE |
| | VISIT HTTP://WWW.CASHACME.COM/RESOURCES/NAECA-2015-REGU |
| | LATIONS/ FOR FURTHER DETAILS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | LUIS A. CRESPO |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |
| | AVAILABLE FROM 1:00 PM TO 4:00 PM |
| | [email protected] |
| | 561-805-6720 |
| | |