| 2018-06-20 17:36:47 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | REVISED TRUSS DRAWINGS DENIED BY BUILDING |
| | |
| | 1) TRUSS TO TRUSS CONNECTIONS ARE NOT SPECIFIED ON THE |
| | STRUCTURAL PLANS BY THE DESIGNER OF RECORD FOR THE |
| | STRUCTURE. THE NOTE ON THE STRUCTURAL PLANS STATES |
| | "CONNECTION BY TRUSS COMPANY" FOR THESE CONNECTIONS. |
| | THE CONNECTORS THAT ARE TO BE USED FOR THE TRUSS TO |
| | TRUSS CONNECTIONS NEED TO BE SPECIFIED. FBC107.1 |
| | GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF CONSTRUCTION |
| | DOCUMENTS, STATEMENT OF SPECIAL INSPECTIONS, |
| | GEOTECHNICAL REPORT AND OTHER DATA SHALL BE SUBMITTED |
| | IN TWO OR MORE SETS WITH EACH PERMIT APPLICATION. THE |
| | CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A |
| | REGISTERED DESIGN PROFESSIONAL WHERE REQUIRED BY |
| | CHAPTER 471, FLORIDA STATUTES & 61G15 FLORIDA |
| | ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA STATUTES & |
| | 61G1 FLORIDA ADMINISTRATIVE CODE. WHERE SPECIAL |
| | CONDITIONS EXIST, THE BUILDING OFFICIAL IS AUTHORIZED |
| | TO REQUIRE ADDITIONAL CONSTRUCTION DOCUMENTS TO BE |
| | PREPARED BY A REGISTERED DESIGN PROFESSIONAL. |
| | |
| | 2) THE TRUSS DRAWING COVER PAGE SPECIFIES THE 2017 FBC |
| | AND THIS PROJECT IS PERMITTED UNDER THE 2014 FBC. |
| | PLEASE CORRECT. |
| | |
| | 3) THE TRUSS ANCHOR ID TAGS FOR THE GIRDERS ON REVISED |
| | SHEET S-3 ARE SHOWN AT THE WRONG LOCATIONS. THE LINES |
| | ARE DRAWN TO THE WRONG TRUSSES. FBC 107.2.1 |
| | |
| | 4) THE EXPOSURE CATEGORY ON REVISED SHEET S-3 HAS BEEN |
| | CHANGED FROM THE APPROVED PLANS FROM C TO D AND THE |
| | WIND PRESSURES WERE INCREASED ACCORDINGLY. IN ORDER FOR |
| | THIS CHANGE TO BE APPROVED, THE OTHER PLAN SHEETS FROM |
| | THE APPROVED PLANS THAT SPECIFY THE EXPOSURE CATEGORY |
| | OR THE WIND LOAD PRESSURES WILL ALSO NEED TO BE |
| | REVISED. THE PRODUCT APPROVALS FOR THE COMPONENTS AND |
| | CLADDING WILL NEED TO BE REVIEWED TO SEE IF THEY WILL |
| | COMPLY WITH THE INCREASED PRESSURES FOR EXPOSURE D. FBC |
| | 107.2.1 |
| | |
| | |
| | |
| | |
| | |