| 2018-05-24 09:24:03 | 1ST REVIEW: FBC 2017 6TH ED. RESIDENTIAL |
| | 1ST REVIEW FBC 2017 EXISTING BUILDING |
| | |
| | 1) SUBMIT A FLOOR PLAN OF THE PROPOSED TOILET ROOM |
| | SHOWING THE LENGTH AND WIDTH DIMENSIONS OF THE TOILET |
| | ROOM. |
| | 2) SHOW THE REQUIRED FIXTURE CLEARANCES FOR THE |
| | PLUMBING FIXTURES. COMPLY WITH 2017 FBCR SECS R307, |
| | .P2705. SHOW THE REQUIRED CLEARANCE IN FRONT OF THE |
| | WATER CLOSET AND LAVATORY. |
| | 3) IT APPEARS FROM THE PLANS YOU ARE RUNNING A SEPARATE |
| | BULDING DRAIN FOR THIS HALF BATH AND CONNECTING TO THE |
| | MAIN SEWER ON THE EXTERIOR. IF THAT IS THE CASE, YOU |
| | CANNOT USE AN AIR ADMITTANCE VALE FOR THIS |
| | INSTALLATIONPER MANFACTURER'S INSTALLATION |
| | REQUIREMENTS. EACH BUILSING DRAIN/BUILDING SEWER SHALL |
| | HAVE ONE VENT TO THE ATMOSPHERE. |
| | 4) SHOW THE DOOR SWING ON THE HALF BATH. THE LOCATION |
| | OF DOORS SHALL NOT INTERFERE WITH THE OPERATION OF |
| | DOORS OR WINDOWS. 2017 FBCR SEC.P2705. |
| | 5) BATHROOMS AND OTHER SIMILAR ROOMS SHALL BE PROVIDED |
| | WITH LIGHT AND VENTILATION COMPLYING WITH 2017 FBCR |
| | SEC. R303.3, M1507. |
| | 6) THIS TYPE OF ALTERATION TRIGGERS THE REQUIREMENT FOR |
| | SMOKE ALARMS IN THE DWELLING UNIT PER THE 2017 FBCR |
| | SEC.R314.2.2. |
| | 7) SUBMIT A COMPLETE SET OF PLANS (ELECTRICAL, |
| | MECHANICAL, BUILDING) FOR THE ENTIRE SCOPE OF WORK TO |
| | BE DONE.WPB AMEND. TO FBC SECS.107.3.5, 107.3.5.3. - |
| | MINIMUM REQUIREMENTS FOR PLAN REVIEW. |
| | |