| 2018-05-21 10:11:18 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| | |
| | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| | INSPECTION. |
| | |
| | |
| | 1) THERE DOES NOT APPEAR TO SUFFICIENT SMOKE ALARMS AND |
| | DETECTORS INDCATED ON THE PLAN. |
| | |
| | AS THESE MAY BE BATTERY POWERED PLEASE ENSURE THEY ARE |
| | INSTALLED PER THE CODE. A FIRE INSPECTOR SHALL INSPECT |
| | ON FIRE FINAL. |
| | |
| | |
| | 31.3.4.4 DETECTION. |
| | |
| | 31.3.4.5 SMOKE ALARMS. |
| | 31.3.4.5.1* IN BUILDINGS OTHER THAN THOSE EQUIPPED |
| | THROUGHOUT WITH AN |
| | EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM, |
| | SMOKE ALARMS |
| | SHALL BE INSTALLED IN ACCORDANCE WITH 9.6.2.10, AS |
| | MODIFIED BY 31.3.4.5.2, |
| | OUTSIDE EVERY SLEEPING AREA IN THE IMMEDIATE VICINITY |
| | OF THE BEDROOMS |
| | AND ON ALL LEVELS OF THE DWELLING UNIT, INCLUDING |
| | BASEMENTS. |
| | |
| | 31.3.4.5.3 IN BUILDINGS OTHER THAN THOSE EQUIPPED |
| | THROUGHOUT WITH AN |
| | EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM OR |
| | A COMPLETE, |
| | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| | WITH 31.3.5, |
| | SMOKE ALARMS SHALL BE INSTALLED IN EVERY SLEEPING AREA |
| | IN |
| | ACCORDANCE WITH 9.6.2.10, AS MODIFIED BY 31.3.4.5.4. |
| | 31.3.4.5.4 SMOKE ALARMS REQUIRED BY 31.3.4.5.3 SHALL BE |
| | PERMITTED TO BE |
| | BATTERY POWERED. |
| | |
| | 9.6.2.10 SMOKE ALARMS. |
| | 9.6.2.10.4* SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT |
| | BE |
| | INSTALLED WITHIN AN AREA OF EXCLUSION DETERMINED BY A |
| | 10 FT (3.0 M) |
| | RADIAL DISTANCE ALONG A HORIZONTAL FLOW PATH FROM A |
| | STATIONARY OR |
| | FIXED COOKING APPLIANCE, UNLESS LISTED FOR INSTALLATION |
| | IN CLOSE |
| | PROXIMITY TO COOKING APPLIANCES. SMOKE ALARMS AND SMOKE |
| | DETECTORS INSTALLED BETWEEN 10 FT (3.0 M) AND 20 FT |
| | (6.1 M) ALONG A |
| | HORIZONTAL FLOW PATH FROM A STATIONARY OR FIXED COOKING |
| | APPLIANCE |
| | SHALL BE EQUIPPED WITH AN ALARM-SILENCING MEANS OR USE |
| | PHOTOELECTRIC DETECTION. |
| | EXCEPTION: SMOKE ALARMS OR SMOKE DETECTORS THAT USE |
| | PHOTOELECTRIC DETECTION SHALL BE PERMITTED FOR |
| | INSTALLATION AT A |
| | RADIAL DISTANCE GREATER THAN 6FT (1.8 M) FROM ANY |
| | STATIONARY OR |
| | FIXED COOKING APPLIANCE WHEN THE FOLLOWING CONDITIONS |
| | ARE MET: |
| | (1) THE KITCHEN OR COOKING AREA AND ADJACENT SPACES |
| | HAVE NO |
| | CLEAR INTERIOR PARTITIONS OR HEADERS |
| | (2) THE 10 FT (3.0 M) AREA OF EXCLUSION WOULD PROHIBIT |
| | THE |
| | PLACEMENT OF A SMOKE ALARM OR SMOKE DETECTOR REQUIRED |
| | BY |
| | OTHER SECTIONS OF THIS NFPA 72. |
| | [72:29.8.3.4(4)] |
| | 9.6.2.10.5* SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT |
| | BE |
| | INSTALLED WITHIN A 36 IN. (910 MM) HORIZONTAL PATH FROM |
| | A DOOR TO A |
| | BATHROOM CONTAINING A SHOWER OR TUB UNLESS LISTED FOR |
| | INSTALLATION IN |
| | CLOSE PROXIMITY TO SUCH LOCATIONS. [72:29.8.3.4 (6) ] |
| | 9.6.2.10.6 SYSTEM SMOKE DETECTORS IN ACCORDANCE WITH |
| | NFPA 72, |
| | NATIONAL FIRE ALARM AND SIGNALING CODE, AND ARRANGED TO |
| | FUNCTION IN THE SAME MANNER AS SINGLE-STATION OR |
| | MULTIPLE-STATION |
| | SMOKE ALARMS SHALL BE PERMITTED IN LIEU OF SMOKE |
| | ALARMS. |
| | 9.6.2.10.7 SMOKE ALARMS, OTHER THAN BATTERY-OPERATED |
| | SMOKE |
| | ALARMS AS PERMITTED BY OTHER SECTIONS OF THIS CODE, |
| | SHALL BE |
| | POWERED IN ACCORDANCE WITH THE REQUIREMENTS OF NFPA 72, |
| | NATIONAL FIRE ALARM AND SIGNALING CODE. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| | REFERNECE. |
| | |