| Plan Review Notes For Permit 18050512 |
| Permit Number |
18050512 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-06-07 14:21:44 | 1) THE WATER SUPPLY VALVES FOR THE STACKABLE | | | WASHER/DRYER UNIT SHALL BE PROVIDED WITH ACCESS. 2017 | | | FBC-PLUMBING SEC.606.3. | | | 2) SHT. A-13 - SHOW THE WIDTH OF THE SHOWER IN UNIT #4 | | | ON THE FLOOR PLANS. THE SIZE OF THE SHOWER SHALL COMPLY | | | WITH 2017 FBCV-PLUMBING SEC. 417.4. | | | 3) SHOW THE FIXTURE CLEARANCES OF THE PLUMBING FIXTURES | | | IN ALL THE UNITS PER 2017 FBC-PLUMBING SEC.405. | | | 4) SUBMIT FIRESTOPPING DETAILS FOR ALL PIPE PENTRATIONS | | | THROUGH THE FLOOR TO THE 2ND FLOOR. | | | 5) THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER PIPING | | | FROM THE SOURCE OF HOT WATER TO THE FIXTURES THAT | | | REQUIRE HOT OR TEMPERED WATER SHALL NOT EXCEED 50 FEET | | | PER 2017 FBC-PLUMBING SEC.607.2. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | |
|