| 2018-06-11 09:38:10 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18050512 |
| | UNITS 1 & 2 |
| | 6/11/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW |
| | AC SYSTEMS- SECTION 312.1 FBC M. |
| | |
| | 2) INDICATE HOW THE APARTMENTS ARE TO BE VENTILATED- |
| | NATURALLY IN ACCORDANCE WITH SECTION 402 FBC M, OR |
| | MECHANICALLY PER SECTION 403 FBC M. CHOOSE WHICHEVER |
| | METHOD AND PROVIDE CALCULATIONS. |
| | |
| | 3) DESIGN CRITERIA: PROVIDE A LIST OF CURRENT CODES AND |
| | STANDARDS USED IN THE DESIGN OF THE PROPOSED PROJECT. |
| | |
| | 4) INDICATE THE"CLASSIFICATION OF WORK" FOR THE |
| | PROPOSED PROJECT IN ACCORDANCE WITH SECTIONS 502, 503, |
| | 504, 505, 506, 507, 508, & 09 FBC EX. |
| | |
| | 5) SHEET M1: THE 2ND FLOOR AC CLOSET DOOR SHALL BE |
| | NON-COMBUSTIBLE OR HAVE A FLAME SPREAD INDEX OF NOT |
| | MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE |
| | THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E84 OR UL |
| | 723. |
| | |
| | 6) M1: THE PLANS INDICATE FIRE PLACES IN THE LIVING |
| | ROOMS OF THE1ST AND 2ND FLOOR APARTMENTS. PROVIDE |
| | COMPLETE INFOMATION ABOUT THESE UNITS- MAKES AND MODEL |
| | NUMBERS, TYPE OF FUEL, COMBUSTION AIR, VENTING PLANS, |
| | CLEARANCES TO COMBUSTIBLES ETC. MANUFACTURER'S |
| | SPECIFICATIONS MUST BE SUBMITTED WITH APPROVAL STAMPS |
| | BY THE EOR- SECTIONS 903 & 905 FBC M, AND SECTIONS 602, |
| | 604, & 605 FBC FG. |
| | |
| | 7) M1: SUBMIT MANUFACTURER'S SPECIFICATION FOR THE |
| | DRYER, RECIRCULATION HOOD, AND THE RANGE- SECTIONS |
| | 504.1,505.1, & 917.1, FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |