2018-06-06 13:49:15FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E-1
  
 SMOKE ALARM MISSING AT THE BOTTOM OF THE STAIRWAY FOR
 THE SECOND FLOOR UNIT. ONE ON EACH LEVEL.
  
 R314.3 SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
  
 3.ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING
 BASEMENTS AND HABITABLE ATTICS AND NOT INCLUDING CRAWL
 SPACES AND UNINHABITABLE ATTICS. IN DWELLINGS OR
 DWELLING UNITS WITH SPLIT LEVELS AND WITHOUT AN
 INTERVENING DOOR BETWEEN THE ADJACENT LEVELS, A SMOKE
 ALARM INSTALLED ON THE UPPER LEVEL SHALL SUFFICE FOR
 THE ADJACENT LOWER LEVEL PROVIDED THAT THE LOWER LEVEL
 IS LESS THAN ONE FULL STORY BELOW THE UPPER LEVEL.
  
 4.SMOKE ALARMS SHALL BE INSTALLED NOT LESS THAN 3 FEET
 (914 MM) HORIZONTALLY FROM THE DOOR OR OPENING OF A
 BATHROOM THAT CONTAINS A BATHTUB OR SHOWER UNLESS THIS
 WOULD PREVENT PLACEMENT OF A SMOKE ALARM REQUIRED BY
 SECTION R314.3.
  
 R314.3.1INSTALLATION NEAR COOKING APPLIANCES
 .
 SMOKE ALARMS SHALL NOT BE INSTALLED IN THE FOLLOWING
 LOCATIONS UNLESS THIS WOULD PREVENT PLACEMENT OF A
 SMOKE ALARM IN A LOCATION REQUIRED BY SECTION R314.3.
  
 1.IONIZATION SMOKE ALARMS SHALL NOT BE INSTALLED LESS
 THAN 20 FEET (6096 MM) HORIZONTALLY FROM A PERMANENTLY
 INSTALLED COOKING APPLIANCE.
  
 2.IONIZATION SMOKE ALARMS WITH AN ALARM-SILENCING
 SWITCH SHALL NOT BE INSTALLED LESS THAN 10 FEET (3048
 MM) HORIZONTALLY FROM A PERMANENTLY INSTALLED COOKING
 APPLIANCE.
  
 3.PHOTOELECTRIC SMOKE ALARMS SHALL NOT BE INSTALLED
 LESS THAN 6 FEET (1828 MM) HORIZONTALLY FROM A
 PERMANENTLY INSTALLED COOKING APPLIANCE
  
 KITCHEN OUTLET MISSING IN KITCHEN ON COUNTER NEXT TO
 STOVE 12" OR LARGER.
  
  
 PAGE E-2
  
 OUTLET NEEDED ON FRONT AND REAR OF UNIT #4 OUTSIDE
  
 E3901.7 OUTDOOR OUTLETS.
 NOT LESS THAN ONE RECEPTACLE OUTLET THAT IS READILY
 ACCESSIBLE FROM GRADE LEVEL AND LOCATED NOT MORE THAN 6
 FEET, 6 INCHES (1981 MM) ABOVE GRADE, SHALL BE
 INSTALLED OUTDOORS AT THE FRONT AND BACK OF EACH
 DWELLING UNIT HAVING DIRECT ACCESS TO GRADE LEVEL.
 BALCONIES, DECKS, AND PORCHES THAT ARE ACCESSIBLE FROM
 INSIDE OF THE DWELLING UNIT SHALL HAVE AT LEAST ONE
 RECEPTACLE OUTLET INSTALLED WITHIN THE PERIMETER OF THE
 BALCONY, DECK, OR PORCH. THE RECEPTACLE SHALL BE
 LOCATED NOT MORE THAN 6 FEET, 6 INCHES (1981 MM) ABOVE
 THE BALCONY, DECK, OR PORCH SURFACE. [210.52(E)]
  
  
 PAGE E-3
  
 LOAD CALCULATIONS SHOULD BE DONE IN ACCORDANCE WITH THE
 CODE, YOU CAN NOT TAKE A DEMAND ON EACH UNIT AND THEN
 JUST ADD THEM TOGETHER TO GET A TOTAL.
  
 250.94 INTERSYSTEM BONDING SYSTEM REQUIRED