| 2018-06-06 13:49:15 | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | PAGE E-1 |
| | |
| | SMOKE ALARM MISSING AT THE BOTTOM OF THE STAIRWAY FOR |
| | THE SECOND FLOOR UNIT. ONE ON EACH LEVEL. |
| | |
| | R314.3 SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING |
| | LOCATIONS: |
| | |
| | 3.ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING |
| | BASEMENTS AND HABITABLE ATTICS AND NOT INCLUDING CRAWL |
| | SPACES AND UNINHABITABLE ATTICS. IN DWELLINGS OR |
| | DWELLING UNITS WITH SPLIT LEVELS AND WITHOUT AN |
| | INTERVENING DOOR BETWEEN THE ADJACENT LEVELS, A SMOKE |
| | ALARM INSTALLED ON THE UPPER LEVEL SHALL SUFFICE FOR |
| | THE ADJACENT LOWER LEVEL PROVIDED THAT THE LOWER LEVEL |
| | IS LESS THAN ONE FULL STORY BELOW THE UPPER LEVEL. |
| | |
| | 4.SMOKE ALARMS SHALL BE INSTALLED NOT LESS THAN 3 FEET |
| | (914 MM) HORIZONTALLY FROM THE DOOR OR OPENING OF A |
| | BATHROOM THAT CONTAINS A BATHTUB OR SHOWER UNLESS THIS |
| | WOULD PREVENT PLACEMENT OF A SMOKE ALARM REQUIRED BY |
| | SECTION R314.3. |
| | |
| | R314.3.1INSTALLATION NEAR COOKING APPLIANCES |
| | . |
| | SMOKE ALARMS SHALL NOT BE INSTALLED IN THE FOLLOWING |
| | LOCATIONS UNLESS THIS WOULD PREVENT PLACEMENT OF A |
| | SMOKE ALARM IN A LOCATION REQUIRED BY SECTION R314.3. |
| | |
| | 1.IONIZATION SMOKE ALARMS SHALL NOT BE INSTALLED LESS |
| | THAN 20 FEET (6096 MM) HORIZONTALLY FROM A PERMANENTLY |
| | INSTALLED COOKING APPLIANCE. |
| | |
| | 2.IONIZATION SMOKE ALARMS WITH AN ALARM-SILENCING |
| | SWITCH SHALL NOT BE INSTALLED LESS THAN 10 FEET (3048 |
| | MM) HORIZONTALLY FROM A PERMANENTLY INSTALLED COOKING |
| | APPLIANCE. |
| | |
| | 3.PHOTOELECTRIC SMOKE ALARMS SHALL NOT BE INSTALLED |
| | LESS THAN 6 FEET (1828 MM) HORIZONTALLY FROM A |
| | PERMANENTLY INSTALLED COOKING APPLIANCE |
| | |
| | KITCHEN OUTLET MISSING IN KITCHEN ON COUNTER NEXT TO |
| | STOVE 12" OR LARGER. |
| | |
| | |
| | PAGE E-2 |
| | |
| | OUTLET NEEDED ON FRONT AND REAR OF UNIT #4 OUTSIDE |
| | |
| | E3901.7 OUTDOOR OUTLETS. |
| | NOT LESS THAN ONE RECEPTACLE OUTLET THAT IS READILY |
| | ACCESSIBLE FROM GRADE LEVEL AND LOCATED NOT MORE THAN 6 |
| | FEET, 6 INCHES (1981 MM) ABOVE GRADE, SHALL BE |
| | INSTALLED OUTDOORS AT THE FRONT AND BACK OF EACH |
| | DWELLING UNIT HAVING DIRECT ACCESS TO GRADE LEVEL. |
| | BALCONIES, DECKS, AND PORCHES THAT ARE ACCESSIBLE FROM |
| | INSIDE OF THE DWELLING UNIT SHALL HAVE AT LEAST ONE |
| | RECEPTACLE OUTLET INSTALLED WITHIN THE PERIMETER OF THE |
| | BALCONY, DECK, OR PORCH. THE RECEPTACLE SHALL BE |
| | LOCATED NOT MORE THAN 6 FEET, 6 INCHES (1981 MM) ABOVE |
| | THE BALCONY, DECK, OR PORCH SURFACE. [210.52(E)] |
| | |
| | |
| | PAGE E-3 |
| | |
| | LOAD CALCULATIONS SHOULD BE DONE IN ACCORDANCE WITH THE |
| | CODE, YOU CAN NOT TAKE A DEMAND ON EACH UNIT AND THEN |
| | JUST ADD THEM TOGETHER TO GET A TOTAL. |
| | |
| | 250.94 INTERSYSTEM BONDING SYSTEM REQUIRED |