| Plan Review Notes For Permit 18050503 |
| Permit Number |
18050503 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-05-19 05:50:18 | 1) THE ADDRESS ON THE GAS PLAN IS 112 POTTER RD, AND | | | THE ADDRESS FOR THE POOL IS 120 RD. CLARIFY. | | | 2) SUBMIT A CLEAR AND LEGIBLE GAS RISER FOR REVIEW.PIPE | | | SIZES, TYPE OF PIPE AND SOME DISTANCES ARE ILLEGBLE AND | | | A COMPREHENSIVE REVIEW COULD NOT BE DONE DUE TO THE | | | PRINTING BEING EXTREMELY DIFFICULT TO READ. WPB AMEND. | | | TO FBC SEC. 107.2.1. | | | 3) SHOW THE EHD OF 1/2 INCH CSST. WPB AMEND. TO FBC | | | SEC. 107.2.1. | | | 4) CLEARLY SHOW THE LENGTHS OF ALL CUT SECTIONS OF | | | PIPE. 2017 FBCR SEC.G2413.4.1, G2413.4.2. | | | 5) MANUF. SPECS FOR ALL APPLIANCES & EQUIPMENT SHALL BE | | | SUBMITTED FOR REVIEW. 2017 FBCR SEC. G2404.3. | | | 6) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE | | | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE | | | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR | | | INSTALLATION. 2017 FGC SEC.410.1, 2017 FBC-RES. SEC. | | | G2421.1. | | | 7) PIPING THRU WALL TO INTERIOR SHALL BE SLEEVED / | | | PROTECTED. | | | 8) SHOW THE SIZE OF THE BRANCH LINES TO THE POOL HEATER | | | AND THE GENERATOR. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | |
|