Plan Review Notes
Plan Review Notes For Permit 18050501
Permit Number 18050501
Review Stop P
Sequence Number 1
Notes
Date Text
2018-05-19 05:15:521) SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS PER 2013
 APSP-7 SEC. 4.4.9.THE TDH CALCULATIONS SHALL BE THE
 TOTAL FRICTION LOSS OF ALL SYSTEM COMPONENTS EXCEPT THE
 PUMP. THE MAXIMUM FLOW OF THE PUMP FROM THE PUMP CURVE
 CAN NO LONGER BE USED TO DETEREMINE MAXIMUM SYSTEM FLOW
 RATE.
 2) WHY HAS A SURVEY FOR LOT 30 BEEN SUBMITTED? CLARIFY.
 3) SHT. 2 OF 2 - GENERAL NOTES - PLEASE REVISE NOTE #8
 - THE 2013 EDITION OF APSP 7 IS IN EFFECT, NOT 2006.
 THIS ALSO OCCURS IN NOTE #16.
 4) GENERAL NOTE #15 REFERS TO THE 2014 FBC.REVISE TO
 2017 FBC.
 5) AN REDUCED PRESSURE ZONE BACKFLOW DEVICE IS REQUIRED
 AT THE WATER METER AND A PRESSURE VACUUM BREAKER
 BACKFLOW DEVICE IS REQUIRED ON THE AUTOFILL PER CITY OF
 WPB CROSS CONNECTION CONTROL MANUAL & FBC-PLUMBING
 SEC.608 & TABLE 608.1.
 6) THE VACUUM LINE SHALL BE EQUIPPED WITH A VALVE TO
 REMAIN IN THE CLOSED POSITION WHEN NOT IN USE. APSP 7
 SEC.4.6.
 7)
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  