| Plan Review Notes For Permit 18050501 |
| Permit Number |
18050501 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-05-22 09:58:56 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE ADDRESS ON THE PLANS, 112 POTTER ROAD, DOES NOT | | | MATCH THE ADDRESS LISTED ON THE APPLICATION, 120 POTTER | | | ROAD. FBC 107.2.1 | | | | | | 2) NOTE: FBC-R4501.19 FINAL INSPECTION. FINAL | | | ELECTRICAL AND BARRIER CODE INSPECTION SHALL BE | | | COMPLETED PRIOR TO FILLING THE POOL WITH WATER. | | | | | | 3) THE PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD | | | AREA (AE FLOOD ZONE). THE POOL EQUIPMENT SHALL BE | | | ELEVATED TO OR ABOVE THE FINISH FLOOR ELEVATION OF THE | | | LIVING SPACE OF THE DWELLING UNIT. FBC-R322 | | | | | | 4) SUBMIT TWO SETS OF THE MANUFACTURER'S SPECIFICATIONS | | | AND PRODUCT LISTING THAT SHOWS COMPLIANCE WITH UL 2017 | | | FOR THE WINDOW AND DOOR ALARMS. FBC 107.2.1.2 |
|