| 2018-05-18 05:58:45 | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. | | | | | | SEE RED-LINE CORRECTIONS MADE TO PLAN. | | | | | | 1. FEEDER TO 200AMP MB PANEL SHOWS 3-3/0 CU OR AL. | | | 3/0 AL NOT RATED FOR 200AMP FEEDER. WILL BE 3-2/0 CU OR | | | 3-4/0 AL. | | | 310.15B7 (2) NEC | | | | | | 2. PLAN SHOWS 2-2/0 CU FROM METER CAN TO SERVICE | | | DISCONNECT. GROUNDED CONDUCTOR REQUIRED AT SERVICE | | | DISCONNECT. | | | PLAN RED-LINED TO SHOW 3-2/0 CU | | | 250.24(C) NEC | | | | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WPB | | | [email protected] | | | CELL: 561-657-1653 | | | |
|