Plan Review Notes
Plan Review Notes For Permit 18050484
Permit Number 18050484
Review Stop E
Sequence Number 1
Notes
Date Text
2018-05-31 15:10:00FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E-DEW-02A
  
 CLOUDED AREA AT BOTTOM SHOWING FP NEED TO KNOW WHAT
 CIRCUITS ARE NEEDED AND SIZES AND WHERE FED FROM.
  
  
 PAGE E-DEW-15A
  
 SHOW LOCATION OF FIRE PUMP IN BUILDING. THE BLOWUP OF
 THE ROOM DOES NOT SHOW WHERE IT IS LOCATED.
  
 FIRE PUMP SKID AS A DESCRIPTION IS NOT ACCEPTABLE WHAT
 SIZE IS THE PUMP DOES IT HAVE AND CONTROLLER IF SO
 SUBMIT ALL PAPER WORK SHOWING LISTINGS FOR ALL FIRE
 PUMP EQUIPMENT.
  
 SOURCES OF POWER ARE THESE FROM FPL CITY DOES NOT
 ACCEPT FPL AS A RELIABLE SOURCE.
  
 HOW DO THE FEEDS ENTER THE BUILDING?? UNDERGROUND? WHAT
 TYPE OF PIPE? SIZE OF CONDUCTORS?
  
  
 REVISION SHOWS NO ADDED VALUE FOR THE FIRE PUMP AND
 CONTROLLER PLEASE ADD TO NEXT REVISION.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO
 PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG
 WITH THE CITY RESUBMITTAL FORM. ADDITIONALLY, INSERT
 CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE OR VOID THE PREVIOUSLY REVIEWED
 SHEETS.