Plan Review Notes
Plan Review Notes For Permit 18050483
Permit Number 18050483
Review Stop E
Sequence Number 1
Notes
Date Text
2018-05-20 12:26:38CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; WPB FBC
 107.3.5
 3. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE
 CORRECTION. NEC 210.12
 4. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D)
 5. RECEPTACLES IN KITCHEN REQUIRE GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8
 6. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12
 7. THE WALL SPACING REQUIREMENTS FOR KITCHEN COUNTER
 SPACE STATE THAT RECEPTACLE OUTLETS SHALL BE INSTALLED
 SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24
 INCHES MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET
 IN THAT SPACE. THE PLAN PROVIDED DOES NOT MEET THIS
 CODE IN SOME AREAS. PROVIDE CORRECTION. NEC
 210.52(C)(1)
 8. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN.
 PROVIDE CORRECTION FOR MASTER BATH. NEC 210.11(C)(3),
 210.52(D)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER