2018-05-22 10:27:081) INDICATE THE TYPE OF PIPE FOR THE EXISTING 1 INCH
 GAS LINE TO THE EXISTING GAS LOADS.
 2) THE 1 INCH METALLIC PIPE DOWNSTREAM OF THE MP
 REGULATOR AT THE GENERATOR SHALL BE 1 INCH PER TABLE
 402.4(2) OF THE 2017 FBC-FUEL GAS CODE.
 3) THE PLAN REFERS TO TABLE 402.4 (35) OF THE 2017
 FBC-FUEL GAS CODE. THIS TABLE IS FOR PROPANE GAS. THE
 CORRECT TABLE IS 402.4 (22).
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW