| 2018-05-15 13:44:42 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| | |
| | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| | INSPECTION. |
| | |
| | |
| | 1) THERE IS NO INDICATION OF COMPLIANCE WITH THE |
| | CURRENT EDITION OF THE FLORIDA FIRE PREVENTION CODE. |
| | |
| | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| | 6TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| | THE 2015 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| | APPLICABLE CODES OR STANDARDS. |
| | |
| | THERE DOES NOT APPEAR TO BE ANY CONFLICT; HOWEVER, |
| | PLEASE TAKE NOTE AND ENSURE COMPLIANCE AS THAT IS HOW |
| | IT WILL BE INSPECTED BY FIRE INSPECTORS. |
| | |
| | |
| | |
| | 2) SHEET E 1 - THERE IS AN EXIT SIGN INDICATED AT THE |
| | END OF THE REAR CORRIDOR LEADING INTO A CONFERNECE |
| | ROOM. FROM THE CONFERNECE ROOM THERE IS A DOOR LEADING |
| | TO THE WAREHOUSE AND AN EXIT FROM THE WAREHOUSE. |
| | |
| | THE OCCUPANCY CAN SUUPORT THE ONE EXIT AT THE FRONT, |
| | BUT THE EXIT SIGN AT THE CONFERENCE ROOM DOOR NEEDS TO |
| | BE MOVE TO INSIDE THE CONFERENCE ROOM LEADING TO THE |
| | CORRIDOR. |
| | |
| | THE WAREHOUSE EXIT SIGN CAN STAD ALONE FROM THAT AREA. |
| | |
| | PER NFPA 101, CHAPTER 38 NEW BUSINESS |
| | |
| | 38.2 MEANS OF EGRESS REQUIREMENTS. |
| | 38.2.1 GENERAL. |
| | 38.2.1.1 ALL MEANS OF EGRESS SHALL BE IN ACCORDANCE |
| | WITH CHAPTER 7 AND |
| | THIS CHAPTER. |
| | |
| | 38.2.4.3 A SINGLE EXIT SHALL BE PERMITTED FOR A ROOM OR |
| | AREA WITH A TOTAL |
| | OCCUPANT LOAD OF LESS THAN 100 PERSONS, PROVIDED THAT |
| | ALL OF THE |
| | FOLLOWING CRITERIA ARE MET: |
| | (1) THE EXIT SHALL DISCHARGE DIRECTLY TO THE OUTSIDE AT |
| | THE LEVEL OF EXIT |
| | DISCHARGE FOR THE BUILDING. |
| | (2) THE TOTAL DISTANCE OF TRAVEL FROM ANY POINT, |
| | INCLUDING TRAVEL WITHIN |
| | THE EXIT, SHALL NOT EXCEED 100 FT (30 M). |
| | (3) THE TOTAL DISTANCE OF TRAVEL SPECIFIED IN |
| | 38.2.4.3(2) SHALL BE ON THE |
| | SAME STORY, OR, IF TRAVERSING OF STAIRS IS NECESSARY, |
| | SUCH STAIRS SHALL |
| | NOT EXCEED 15 FT (4570 MM) IN HEIGHT, AND BOTH OF THE |
| | FOLLOWING |
| | ALSO SHALL APPLY: |
| | (A) INTERIOR STAIRS SHALL BE PROVIDED WITH COMPLETE |
| | ENCLOSURES TO |
| | SEPARATE THEM FROM ANY OTHER PART OF THE BUILDING, WITH |
| | NO |
| | DOOR OPENINGS THEREIN. |
| | (B) A SINGLE OUTSIDE STAIR IN ACCORDANCE WITH 7.2.2 |
| | SHALL BE |
| | PERMITTED TO SERVE ALL STORIES PERMITTED WITHIN THE 15 |
| | FT (4570 |
| | MM) VERTICAL TRAVEL LIMITATION |
| | |
| | PER NFPA 101, CHAPTER 7 MEANS OF EGRESS. |
| | |
| | 7.5.1.6 EXIT ACCESS FROM ROOMS OR SPACES SHALL BE |
| | PERMITTED TO BE |
| | THROUGH ADJOINING OR INTERVENING ROOMS OR AREAS, |
| | PROVIDED THAT SUCH |
| | ROOMS OR AREAS ARE ACCESSORY TO THE AREA SERVED. |
| | FOYERS, LOBBIES, AND |
| | RECEPTION ROOMS CONSTRUCTED AS REQUIRED FOR CORRIDORS |
| | SHALL NOT BE |
| | CONSTRUED AS INTERVENING ROOMS. EXIT ACCESS SHALL BE |
| | ARRANGED SO |
| | THAT IT IS NOT NECESSARY TO PASS THROUGH ANY AREA |
| | IDENTIFIED UNDER |
| | PROTECTION FROM HAZARDS IN CHAPTERS 11 THROUGH 43. |
| | |
| | PLEASE CHANGE THE LOCATION OF THE REAR EXIT SIGN. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |