| 2018-06-07 15:01:45 | 06/07/2018 2ND INTERCEPTOR REVIEW**DENIED** |
| | |
| | 1) TRASH CAN WASH MUST BE VENTED. FBC P 901.2.1 |
| | |
| | 2) NO SIZING OF INTERCEPTOR PROVIDED. 1003.3.4 |
| | HYDROMECHANICAL GREASE INTERCEPTORS, FATS, OILS AND |
| | GREASES DISPOSAL SYSTEMS AND AUTOMATIC GREASE REMOVAL |
| | DEVICES. |
| | HYDROMECHANICAL GREASE INTERCEPTORS; FATS, OILS, AND |
| | GREASES DISPOSAL SYSTEMS AND AUTOMATIC GREASE REMOVAL |
| | DEVICES SHALL BE SIZED IN ACCORDANCE WITH ASME |
| | A112.14.3, ASME A112.14.4, ASME A112.14.6, CSA B481.3 |
| | OR PDI G101. HYDROMECHANICAL GREASE INTERCEPTORS; FATS, |
| | OILS, AND GREASES DISPOSAL SYSTEMS; AND AUTOMATIC |
| | GREASE REMOVAL DEVICES SHALL BE DESIGNED AND TESTED IN |
| | ACCORDANCE WITH ASME A112.14.3, ASME A112.14.4, CSA |
| | B481.1, PDI G101 OR PDI G102. HYDROMECHANICAL GREASE |
| | INTERCEPTORS; FATS, OILS, AND GREASES DISPOSAL SYSTEMS; |
| | AND AUTOMATIC GREASE REMOVAL DEVICES SHALL BE INSTALLED |
| | IN ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTIONS. |
| | WHERE MANUFACTURER?S INSTRUCTIONS ARE NOT PROVIDED, |
| | HYDROMECHANICAL GREASE INTERCEPTORS; FATS, OILS, AND |
| | GREASES DISPOSAL SYSTEMS; AND AUTOMATIC GREASE REMOVAL |
| | DEVICES SHALL BE INSTALLED IN COMPLIANCE WITH ASME |
| | A112.14.3, ASME A112.14.4, ASME A112.14.6, CSA B481.3 |
| | OR PDI G101. |
| | |
| | EXCEPTION: GREASE INTERCEPTORS THAT ARE SIZED, |
| | CONSTRUCTED AND APPROVED IN ACCORDANCE WITH RULE 64E-6, |
| | FLORIDA ADMINISTRATIVE CODE AND THAT ARE LOCATED |
| | OUTSIDE THE BUILDING SHALL NOT BE REQUIRED TO MEET THE |
| | REQUIREMENTS OF THIS SECTION. |
| | |
| | 1003.3.4.1GREASE INTERCEPTOR CAPACITY. |
| | GREASE INTERCEPTORS SHALL HAVE THE GREASE RETENTION |
| | CAPACITY INDICATED IN TABLE 1003.3.4.1 FOR THE |
| | FLOW-THROUGH RATES INDICATED. |
| | |
| | 3) SPECIFICATION FOR INTERCEPTOR ON PLAN ARE TOO SMALL |
| | AND CAN NOT BE READ. FBC 107.2.5 |
| | |
| | 4) VALUE IS TOO LOW. PROVIDE A SIGNED BONA FIDE |
| | CONTRACT SHOW ALL COST INCLUDING THE GREASE INTERCEPTOR |
| | AS IT WAS NOT INCLUDED WITH THE MAIN PERMIT. FBC 109.3 |
| | |
| | |
| | TIM HUNT |
| | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER |
| | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | 561-805-6695 |
| | [email protected] |
| | |
| | |