| 2018-06-13 17:08:24 | BUILDING PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER, PX3169 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 2ND REVIEW |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | COMMENTS FROM 1ST REVIEW HAVE NOT BEEN ADDRESSED. |
| | |
| | 1. COMPLIED |
| | |
| | R301.2.1 WIND DESIGN CRITERIA. |
| | BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN |
| | ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING |
| | THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED |
| | FROM FIGURE R301.2(4). THE STRUCTURAL PROVISIONS OF |
| | THIS CODE FOR WIND LOADS ARE NOT PERMITTED WHERE WIND |
| | DESIGN IS REQUIRED AS SPECIFIED IN SECTION R301.2.1.1. |
| | WHERE DIFFERENT CONSTRUCTION METHODS AND STRUCTURAL |
| | MATERIALS ARE USED FOR VARIOUS PORTIONS OF A BUILDING, |
| | THE APPLICABLE REQUIREMENTS OF THIS SECTION FOR EACH |
| | PORTION SHALL APPLY. WHERE NOT OTHERWISE SPECIFIED, THE |
| | WIND LOADS LISTED IN TABLE R301.2(2) ADJUSTED FOR |
| | HEIGHT AND EXPOSURE USING TABLE R301.2(3) SHALL BE USED |
| | TO DETERMINE DESIGN LOAD PERFORMANCE REQUIREMENTS FOR |
| | WALL COVERINGS, CURTAIN WALLS, ROOF COVERINGS, EXTERIOR |
| | WINDOWS, SKYLIGHTS AND EXTERIOR DOORS (OTHER THAN |
| | GARAGE DOORS). |
| | |
| | 2. DESIGNER TO PRINT NAME AND SIGN PLAN. |
| | FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO |
| | SECTION 107.3.5) AND F.S. 481.229. |
| | |
| | 3. ALL SUBMITTAL DOCUMENTS SHALL BE SUBMITTED IN |
| | DUPLICATE. |
| | FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF |
| | CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL |
| | INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL |
| | BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT |
| | APPLICATION. |
| | |
| | 4. PROVIDE PRODUCT APPROVALS FOR WINDOW MULLIONS. |
| | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | SPECIFICALLY, PROVIDE WINDOW MULLION SUBMITTALS. |
| | |
| | |
| | DUE TO THE DEFICIENCIES OF THIS PLAN, A COMPLETE AND |
| | THOROUGH REVIEW CANNOT BE PERFORMED AT THIS TIME. UPON |
| | RE-SUBMITTAL, ADDITIONAL COMMENTS MAY BE MADE. |
| | |
| | |