| Plan Review Notes For Permit 18050426 |
| Permit Number |
18050426 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-06-30 06:04:45 | 1) SUBMIT NEW GREASE TRAP SIZING CALCULATIONS. THE | | | SIZING CALCULATIONS ON THE PLANS DO NOT APPEAR TO | | | COMPLY WITH THE SIZING EQUATION IN FL. ADMIN. CODE RULE | | | 64E-6.013 (7) (D) OR PDI STANDARD G-101 IF THAT IS YOUR | | | INTENT. CLARIFY AND SUBMIT CORRECT SIZING CALCULATIONS | | | FOR THE UNIT. | | | 2) INSTALLATION SHEETS FOR ZURN GREASE TRAPS HAVE BEEN | | | SUBMITTED BUT SPECS FOR A JR SMITH UNIT HAVE ALSO BEEN | | | SUBMITTED. WHICH IS IT? CLARIFY. | | | 3) SUBMIT TWO COPIES OF ALL DOCUMENTS. WPB AMEND. TO | | | FBC SEC. 107.2.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|