Plan Review Notes
Plan Review Notes For Permit 18050426
Permit Number 18050426
Review Stop P
Sequence Number 2
Notes
Date Text
2018-06-30 06:04:451) SUBMIT NEW GREASE TRAP SIZING CALCULATIONS. THE
 SIZING CALCULATIONS ON THE PLANS DO NOT APPEAR TO
 COMPLY WITH THE SIZING EQUATION IN FL. ADMIN. CODE RULE
 64E-6.013 (7) (D) OR PDI STANDARD G-101 IF THAT IS YOUR
 INTENT. CLARIFY AND SUBMIT CORRECT SIZING CALCULATIONS
 FOR THE UNIT.
 2) INSTALLATION SHEETS FOR ZURN GREASE TRAPS HAVE BEEN
 SUBMITTED BUT SPECS FOR A JR SMITH UNIT HAVE ALSO BEEN
 SUBMITTED. WHICH IS IT? CLARIFY.
 3) SUBMIT TWO COPIES OF ALL DOCUMENTS. WPB AMEND. TO
 FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW