2018-05-19 03:50:371) SUBMIT TWO COPIES OF THE INSTALLATION MANUAL FOR THE
 INTERCEPTOR. WPB AMEND. TO FBC SEC. 107.2.1.
 2) IDENTIFY ON THE MANUFACTURER'S SPECS WHICH UNIT IS
 BEING INSTALLED. WPB AMEND. TO FBC SEC. 107.2.1.
 3) THE SIZING CALCULATIONS ON THE PLANS DO NOT APPEAR
 TO COMPLY WITH THE SIZING EQUATION IN FL. ADMIN. CODE
 RULE 64E-6.013 (7) (D) IF THAT IS YOUR INTENT. CLARIFY
 AND SUBMIT CORRECT SIZING CALCULATIONS FOR THE UNIT.
  