| 2018-06-27 12:46:46 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | FROM PREVIOUS REVIEW: |
| | |
| | 1. WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED |
| | SETS OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |
| | 2. THE PROPOSED IMPROVEMENT IS LOCATED IN A SPECIAL |
| | FLOOD HAZARD AREA. SEE CITY OF WEST PALM BEACH |
| | MUNICIPAL CODE SECTION 18-290, ALTHOUGH TEMPORARY |
| | CONSTRUCTION TRAILERS ARE EXEMPT FROM THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, THEY ARE NOT EXEMPT FROM |
| | FLOOD REQUIREMENTS (FEDERAL). |
| | |
| | REVISE PLAN TO SHOW PROPOSED ELEVATION OF THE FINISHED |
| | FLOOR AND/OR DRY FLOODPROOFING. THE DESIGN FLOOD |
| | ELEVATION AT THIS LOCATION IS 14.7 NAVD88 (12.7 BFE + |
| | 2' FREEBOARD). IF ANY PORTION OF THE STRUCTURE |
| | INCLUDING FOUNDATION IS BELOW DFE, IT IS TO BE MADE OF |
| | FLOOD RESISTANT MATERIALS AND BE DESIGNED TO RESIST |
| | FLOOD LOADS; REVISE PLAN ACCORDINGLY. |
| | |
| | 2ND REVIEW: |
| | |
| | SEE THE NOTE ON THE SIGNED AND SEALED PLAN, SHEET C1, |
| | FLOOD NOTES. APPLICANT PROPOSES TO HAVE FINISHED FLOOR |
| | MEET FREEBOARD, BUT BLOCKS ON LIMEROCK BASE WILL BE |
| | BELOW THE DESIGN FLOOD ELEVATION. THIS IS TO RESIST |
| | FLOOD LOADS, BUT IS SPECIFICALLY EXCLUDED FROM THE |
| | ENGINEERING. ADDRESS BY EITHER HAVING ENGINEER DESIGN A |
| | FOUNDATION/SUPPORT WHICH IS DESIGNED TO RESIST FLOOD |
| | LOADS, OR PROPOSE INSTALLATION WHICH MEETS FREEBOARD |
| | REQUIREMENT. |
| | |
| | |