Plan Review Notes
Plan Review Notes For Permit 18050390
Permit Number 18050390
Review Stop M
Sequence Number 2
Notes
Date Text
2018-08-22 11:17:262ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18050390
 8/22/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A PRODUCT DATA SHEET FROM THE MANUFACTURER
 FOR THE 90 MINUTE FIRE-RATED AC CLOSET DOORS 215C,
 315C, AND 415C THAT WILL BE EQUIPPED WITH THE 30"X30'
 RETURN GRILLS AND FIRE DAMPERS. PLEASE CLARIFY WHY THE
 DOORS 101A, 201C, 301C, AND 401C WHICH ARE ALSO AC
 CLOSET DOORS IN THE NW CORRIDOR DO NOT HAVE THE RETURN
 GRILLS AND FIRE DAMPERS, AND WHY THESE DOORS ARE ONLY
 45 MINUTE DOORS.
  
 2) M1.03B: PLEASE REVISE NOTE #7 TO INDICATE CLASS 1
 MOTORIZED DAMPERS.
  
 3) M2.02: THERE IS A MISSING FIRE DAMPER WHERE THE
 10X10 EXHAUST DUCT PENETRATES THE FIRE-RATED TRASH
 ROOM/CORRIDOR WALL- SECTION 607.5.2 FBC M.
  
 4) M2.02: THE 16X6 O/A INTAKE AND EXHAUST REGISTERS IN
 THE EXTERIOR SOFFIT SHALL BE CORROSION RESISTANT AND
 SHALL BE PROTECTED AGAINST WEATHER CONDITIONS- SECTIONS
 401.5 AND 501.3.2 FBC M.
  
 5) M5.03: PLEASE PROVIDE A HORIZONTAL FIRE DAMPER
 DETAIL FOR THE O/A AND EXHAUST RISER DUCTS- SECTION
 607.6.2 FBC M.
  
 6) M3.01: 2ND REQUEST TO REVISE THE OUTDOOR AIR
 CALCULATION SCHEDULE WHICH IS INCORRECTLY INDICATING
 FCU-F FOR THE LAUNDRY INSTEAD OF FCU-C.
  
 7) THE CONDENSER STAND NOA #13-0321.06 HAS BEEN
 SUPERSEDED BY NOA #15-0205.01. PLEASE PROVIDE A COPY OF
 THE NOA WITH APPROVAL STAMP BY THE EOR.
  
 8) PROVIDE A COMPLETE SUBMITTAL PACKAGE IS REQUIRED FOR
 THE GENERATOR INCLUDING THE UL2200 CERTIFICATE OF
 COMPLIANCE, AND ALL MECHANICAL ACCESSORIES INCLUDING
 THE FUEL PIPINGS, VENT AND EXHAUST PIPINGS, WALL
 THIMBLE, TERMINATION CAPS, AND WALL BRACKETS AND
 SUPPORTS. PLEASE NOTE THAT WIND LOAD ENGINEERING WILL
 BE REQUIRED FOR INSTALLATION OF THE EXTERIOR EXHAUST
 VENT ASSEMBLY THAT IS SHOWN ALONG THE EAST WALL BY THE
 GENERATOR ROOM
  
 9) PLEASE REVIEW THE FOLLOWING LIST OF REQUIRED
 SUBMITTALS TO BE APPROVED BY THE DESIGN PROFESSIONAL OF
 RECORD AND SUBMITTED WITH APPROVAL STAMPS.
  
 GENERATOR
 CLOTHES DRYERS (SUBMITTED).
 FIRE/SMOKE DAMPERS
 FIRE DAMPERS
 SMOKE DETECTORS
 O/A MOTORIZED DAMPERS
 AC STANDS
 LOUVERS
 KITCHEN EXHAUST HOODS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
  