| 2018-08-22 11:17:26 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18050390 |
| | 8/22/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE A PRODUCT DATA SHEET FROM THE MANUFACTURER |
| | FOR THE 90 MINUTE FIRE-RATED AC CLOSET DOORS 215C, |
| | 315C, AND 415C THAT WILL BE EQUIPPED WITH THE 30"X30' |
| | RETURN GRILLS AND FIRE DAMPERS. PLEASE CLARIFY WHY THE |
| | DOORS 101A, 201C, 301C, AND 401C WHICH ARE ALSO AC |
| | CLOSET DOORS IN THE NW CORRIDOR DO NOT HAVE THE RETURN |
| | GRILLS AND FIRE DAMPERS, AND WHY THESE DOORS ARE ONLY |
| | 45 MINUTE DOORS. |
| | |
| | 2) M1.03B: PLEASE REVISE NOTE #7 TO INDICATE CLASS 1 |
| | MOTORIZED DAMPERS. |
| | |
| | 3) M2.02: THERE IS A MISSING FIRE DAMPER WHERE THE |
| | 10X10 EXHAUST DUCT PENETRATES THE FIRE-RATED TRASH |
| | ROOM/CORRIDOR WALL- SECTION 607.5.2 FBC M. |
| | |
| | 4) M2.02: THE 16X6 O/A INTAKE AND EXHAUST REGISTERS IN |
| | THE EXTERIOR SOFFIT SHALL BE CORROSION RESISTANT AND |
| | SHALL BE PROTECTED AGAINST WEATHER CONDITIONS- SECTIONS |
| | 401.5 AND 501.3.2 FBC M. |
| | |
| | 5) M5.03: PLEASE PROVIDE A HORIZONTAL FIRE DAMPER |
| | DETAIL FOR THE O/A AND EXHAUST RISER DUCTS- SECTION |
| | 607.6.2 FBC M. |
| | |
| | 6) M3.01: 2ND REQUEST TO REVISE THE OUTDOOR AIR |
| | CALCULATION SCHEDULE WHICH IS INCORRECTLY INDICATING |
| | FCU-F FOR THE LAUNDRY INSTEAD OF FCU-C. |
| | |
| | 7) THE CONDENSER STAND NOA #13-0321.06 HAS BEEN |
| | SUPERSEDED BY NOA #15-0205.01. PLEASE PROVIDE A COPY OF |
| | THE NOA WITH APPROVAL STAMP BY THE EOR. |
| | |
| | 8) PROVIDE A COMPLETE SUBMITTAL PACKAGE IS REQUIRED FOR |
| | THE GENERATOR INCLUDING THE UL2200 CERTIFICATE OF |
| | COMPLIANCE, AND ALL MECHANICAL ACCESSORIES INCLUDING |
| | THE FUEL PIPINGS, VENT AND EXHAUST PIPINGS, WALL |
| | THIMBLE, TERMINATION CAPS, AND WALL BRACKETS AND |
| | SUPPORTS. PLEASE NOTE THAT WIND LOAD ENGINEERING WILL |
| | BE REQUIRED FOR INSTALLATION OF THE EXTERIOR EXHAUST |
| | VENT ASSEMBLY THAT IS SHOWN ALONG THE EAST WALL BY THE |
| | GENERATOR ROOM |
| | |
| | 9) PLEASE REVIEW THE FOLLOWING LIST OF REQUIRED |
| | SUBMITTALS TO BE APPROVED BY THE DESIGN PROFESSIONAL OF |
| | RECORD AND SUBMITTED WITH APPROVAL STAMPS. |
| | |
| | GENERATOR |
| | CLOTHES DRYERS (SUBMITTED). |
| | FIRE/SMOKE DAMPERS |
| | FIRE DAMPERS |
| | SMOKE DETECTORS |
| | O/A MOTORIZED DAMPERS |
| | AC STANDS |
| | LOUVERS |
| | KITCHEN EXHAUST HOODS |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |