Plan Review Notes
Plan Review Notes For Permit 18050390
Permit Number 18050390
Review Stop B
Sequence Number 2
Notes
Date Text
2018-08-27 10:48:07****CORRECTIONS****
 W.P.B. PERMIT: 18050390
 REVIEWED: AUGUST 27, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1- IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
 -PENDING
  
  
 2-6- OK.
  
  
 7- SHEET A0.09 LIFE SAFETY FLOOR PLAN TYPICAL LEVEL:
 TRASH ROOM AND TRASH CHUTE NEED TO BE FIRE RATED. SEC.
 713 FBC.
  
 7-2 2-HR RATING WAS ADDED TO SHEET A6.04, BUT PLEASE
 ADD 2-HOUR RATING TO SHEET A-0.09 TO MATCH.
  
  
 8-19- OK.
  
  
 20-PROVIDE 2 HOUR FIRE RATED ASSEMBLY DETAILS AND
 SPECIFICATIONS FOR POURED CONCRETE SHEARWALLS AT
 STAIRWAYS AND ELEVATOR SHAFT. SEC. 713.4 FBC. DETAILS
 PROVIDED ON SHEET A8.01 IS FOR CONCRETE BLOCK WALLS
 ONLY.
  
 20-2-PROVIDE FIRE RATED LISTED WALL TYPES TO BE USED IN
 ALL FIRE RATED WALL ASSEMBLIES.
  
  
 23- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 A)FLAT ROOF SINGLE PLY ROOFING NOA 15-0203.23
 SUBMITTED. CLEARLY MARK WHICH APPROVED ASSEMBLY IS
 GOING TO BE INSTALLED. NOTE: IF THE SELECTED ASSEMBLY
 DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES,
 THEN SIGNED AND SEALED RAS 117 CALCULATIONS ARE
 REQUIRED.
 B)CONCRETE ROOF TILE NOA 16-0112.07: DESIGNER OF RECORD
 TO SPECIFY ROOF TILE FASTENING METHOD AS REQUIRED BY
 SEC. 107.2.1.1 CITY AMENDMENTS. IF SPECIFYING TILE
 ADHESIVE, THEN PROVIDE PRODUCT APPROVAL FOR LISTED
 ADHESIVE.
 C) OK.
 D) OK.
 E) CHUTE ALUMINUM CAP AS SHOWN ON PLANS.
  
 A-E-DEFERRED SUBMITTALS
  
  
 24- OK.
  
  
 25- PROVIDE COMPLETE TRUSS PACKAGE SUBMITTAL REVIEWED
 BY THE DESIGNER OF RECORD. SEC. 107.3.4.1 CITY
 AMENDMENTS.
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 -DEFERRED TRUSS SUBMITTAL
  
  
 26-30- OK.
  
 31- OK.
  
 32- OK.
  
  
 33- PROVIDE COMPLETE ENGINEERED DETAILS AND
 SPECIFICATIONS FOR THE CONSTRUCTION OF ALL THE ENTRY
 CANOPIES. SEC. 1601.1 FBC.
  
 -DEFFERED CANOPY SUBMITTAL
  
  
 34- FLOORING UNDERLAYMENT (NOTE: THIS MAY BE SUBMITTED
 LATER AS A DEFERRED SUBMITTAL).
 1- SOUND INSULATION MATERIAL:
 A) PROVIDE 2 COPIES OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 6TH EDITION
 (2017).
 B) PROVIDE 2 COPIES OF THE SOUND TRANSMISSION CLASS
 (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90 AS
 REQUIRED BY SEC. 1207.2 OF FBC 6TH EDITION (2017).
 C) PROVIDE 2 COPIES OF THE IMPACT INSULATION CLASS
 (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492 AS
 REQUIRED BY SEC. 1207.3 OF FBC 6TH EDITION (2017).
  
 -DEFFERED FLOORING SUBMITTAL
  
  
 35- OK.
  
 360- VALUATION DECLARED IN THE PERMIT APPLICATION IS
 LOW. SEC. 109.3 CITY AMENDMENTS. UPDATE VALUATION.
 SEC. 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 -PLEASE PROVIDE EVALUATION BASED IN ICC 2018 VALUES
  
  
 37- SEC. 110.7 CITY AMENDMENTS: SHORING. FOR THRESHOLD
 BUILDINGS, SHORING AND ASSOCIATED FORMWORK OR FALSEWORK
 SHALL BE
 DESIGNED AND INSPECTED BY A FLORIDA LICENSED
 PROFESSIONAL ENGINEER, EMPLOYED BY THE PERMIT HOLDER
 OR SUBCONTRACTOR, PRIOR TO ANY REQUIRED MANDATORY
 INSPECTIONS BY THE THRESHOLD BUILDING INSPECTOR. ALL
 SHORING AND RESHORING PROCEDURES, PLANS AND DETAILS
 SHALL BE SUBMITTED TO THE ENFORCEMENT AGENCY
 FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 -DEFERRED SHORING/RE-SHORING SUBMITTAL
 (SEE THRESHOLD REVIEW FOR ADDITIONAL COMMENTS)
  
  
 38-41 OK.
  
  
 SEE LIST BELOW FOR REQUESTED DEFERRED SUBMITTALS:
 1-ROOFING-PENDING TILE ATTACHMENT AND PRODUCT APPROVAL
 AND ENHANCED NAILING (IF APPLICABLE).
 2- THRASH CHUTE AND ALUMINUM CAP AS SHOWN ON PLANS.
 3-TRUSS SUBMITTAL
 4-CANOPY SUBMITTAL
 5-FLOORING SUBMITTAL
 6-THRESHOLD INSPECTION PLAN
 7-SHORING/RE-SHORING SUBMITTAL
 8-HANDRAIL/GUARDRAIL ENGINEERING
  
  
  
  