2018-06-01 15:43:491ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18050390
 6/1/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1.01A & M1.01A: SHOW THE O/A INLET AND
 EXHAUST OUTLET LOCATIONS FOR THE UNITS- SECTIONS 401.4
 AND 501.3.1 FBC M. SUBMIT A FL. PRODUCT APPROVAL OR
 MIAMI-DADE NOA FOR THE LOUVERS- RULE 9N-3 FAC.
  
 2) PROVIDE EXHAUST AND AIR BALANCE CALCULATIONS FOR THE
 TRASH ROOM TO VERIFY COMPLIANCE WITH SECTION 601.2
 EXCEPTION 1.
  
 3) M2.01 & M3.01: PROVIDE MECHANICAL VENTILATION
 CALCULATIONS FOR THE FIRST FLOOR UNITS IN THE OUTDOOR
 AIR CALCULATION SCHEDULE- TABLE 403.3.1 FBC M.
  
 4) M2.02, COMMON LAUNDRY: A) SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE CLOTHES DRYERS- SECTION 504.1
 FBC M. B) SHOW HOW MAKEUP AIR IS BEING PROVIDED AND
 PROVIDE AN AIR BALANCE CALCULATION- SECTION 504.6. C)
 INDICATE THE TYPE OF DRYER DUCTS TO BE INSTALLED AND
 THICKNESSES. D) SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE DRYER PLENUM BOX.
  
 5) M2.02: SHOW THE INLET LOCATION OF THE O/A DUCT THAT
 IS SUPPLYING FCU-5 AND FCU-D. THIS NO SHAFT SHOWN ON
 THE 2ND-4TH PLANS, OR ON THE RISER DRAWINGS ON M4.01.
  
 6) M3.01: THE OUTDOOR AIR CALCULATION SCHEDULE IS
 INCORRECTLY INDICATING FCU-F FOR THE LAUNDRY INSTEAD OF
 FCU-C.
  
 7) M4.01: PLEASE SHOW THE LOCATIONS OF THE RISERS AND
 SHAFTS ON THE MECHANICAL FLOOR PLANS. CORRECTLY
 IDENTIFY THEM AS 2HR FIRE-RATED SHAFT ENCLOSURES IN
 ACCORDANCE WITH SECTION 713 FBC B.
  
 8) PROVIDE WIND LOAD ENGINEERING AND THE DESIGN
 CRITERIA FOR INSTALLATION OF THE ROOFTOP CONDENSERS
 SECTION 301.15 FBC M, AND SECTION 1609 FBC B. PLEASE
 SUBMIT A FL. PRODUCT APPROVAL OR MIAMI-DADE NOA FOR THE
 AC STANDS.
  
 9) PLEASE REVIEW THE FOLLOWING LIST OF REQUITED
 SUBMITTALS TO BE APPROVED BY THE DESIGN PROFESSIONAL OF
 RECORD AND SUBMITTED WITH APPROVAL STAMPS.
  
 GENERATOR
 CLOTHES DRYERS
 FIRE/SMOKE DAMPERS
 FIRE DAMPERS
 SMOKE DETECTORS
 O/A MOTORIZED DAMPERS
 AC STANDS
 LOUVERS
 KITCHEN EXHAUST HOODS
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  