| 2018-05-22 13:43:31 | PERMIT # 18050390 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | 1) PER NFPA 241 SECTION 8.7.2.3, WHERE UNDERGROUND |
| | WATER MAINS AND HYDRANTS ARE TO BE PROVIDED, THEY SHALL |
| | BE INSTALLED, COMPLETED, AND IN SERVICE PRIOR TO |
| | CONSTRUCTION WORK. |
| | SEPARATE PLANS AND PERMITS NEEDED FOR PRIVATE |
| | UNDERGROUND FIRE LINE AND FIRE HYDRANTS. |
| | |
| | 2) SHEET E1.01A: THERE IS A NOTE THAT STATES: "BUILDING |
| | IS FULLY SUPPLIED WITH SPRINKLER SYSTEM; THEREFORE, |
| | SMOKE AND HEAT DETECTORS ARE NOT REQUIRED THROUGHOUT |
| | THE BUILDING......" |
| | PER NFPA 101 - 30.3.4.45: SMOKE ALARMS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH 9.6.2.10 IN EVERY SLEEPING |
| | AREA, OUTSIDE EVERY SLEEPING AREA IN THE IMMEDIATE |
| | VICINITY OF THE BEDROOMS, AND ON ALL LEVELS OF THE |
| | DEWLLING UNIT, INCLUDING BASEMENTS. |
| | |
| | 3) IF, AND WHERE, APPLICABLE: STRUCTURES WITH LIGHT |
| | FRAME FLOOR/ROOF TRUSS CONSTRUCTION SHALL BE IDENTIFIED |
| | WITH A SIGN AFFIXED TO THE BUILDING. |
| | THE SIGN SHALL FEATURE A MALTESE CROSS 8-INCHES WIDE |
| | AND 8-INCHES TALL AND BE OF A BRIGHT RED REFLECTIVE |
| | COLOR AND BEAR THE APPROPRIATE LETTER R/F/RF |
| | DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA |
| | ADMINISTRATIVE CODE 69A-60.0081. |
| | |
| | 4) SHEET FP-2.01: UNIT TYPE "B" APPEARS TO HAVE |
| | INSUFFICIENT FIRE SPRINKLER COVERAGE OF THE LIVING |
| | AREA. |
| | |
| | 5) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER |
| | SYSTEM AND/OR FIRE ALARM SYSTEM. |
| | |
| | |