| 2018-06-06 12:40:54 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. IT APPEARS FROM THE DESIGN THAT THIS IS AN ASSISTED |
| | LIVING FACILITY. WILL THIS FACILITY BE LICENSED AS |
| | ASSISTED LIVING? PROVIDE CLARIFICATION. WPB FBC 107.2.1 |
| | 2. IF THIS IS AN ASSISTED LIVING FACILITY, PROVIDE |
| | DETAILS OF COMPLIANCE WITH THE EMERGENCY ENVIRONMENTAL |
| | CONTROL REQUIRED PER FLORIDA ADMINISTRATIVE CODE, RULE |
| | 58A-5.036 |
| | 3. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| | DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| | SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND |
| | SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN |
| | THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE |
| | INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN |
| | SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC |
| | 105.1, 107.2.1 |
| | 4. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C |
| | EQUIPMENT PER CODE IN THE AC ROOMS. ADDITIONALLY, SOME |
| | OF THE RECEPTACLES SHOWS ON THE ROOF ARE NOT WITHIN 25 |
| | FEET OF THE FURTHEST UNIT. PROVIDE CORRECTIONS. NEC |
| | 210.63 |
| | 5. GROUND WIRE LABELED AS G-5 ON SHEET E-3.01 IS NOT |
| | SIZED PROPERLY. THIS CONDUCTOR MUST BE SIZED FOR THE |
| | 2/0 FEEDERS PER TABLE 250.66. PROVIDE CORRECTION. NEC |
| | 250.66 |
| | 6. GROUNDING ELECTRODE CONDUCTORS FOR EACH MAIN SHOULD |
| | BE TIED TO A COMMON GROUNDING ELECTRODE AND ALL |
| | CONNECTED TOGETHER IN ACCORDANCE WITH CODE. PROVIDE |
| | CORRECTION. THE FIRE PUMP AND GENERATOR GROUNDING |
| | ELECTRODE CONDUCTORS ARE SHOWN SEPARATE. ADDITIONALLY, |
| | THE GENERATOR APPEARS TO NOT BE A SEPARATELY DERIVED |
| | SYSTEM AS IT IS SHOWN WITH A 3 POLE TRANSFER SWITCH. |
| | THEREFORE, IT WOULD NOT BE CODE COMPLIANT TO INSTALL A |
| | GROUNDING ELECTRODE SYSTEM IN THIS LOCATION. PROVIDE |
| | CLARIFICATION AND/OR CORRECTIONS. NEC 250.64(D), 250.30 |
| | 7. LABELING OF MAINS IS CONFUSING. PLAN SHOWS MAIN 3 OF |
| | 3 FOR HOUSE LOADS AND THEN SHOWS MAIN 1 OF 2 FOR |
| | EMERGENCY LOADS ON THE SAME SHEET. IT APPEARS THAT YOU |
| | WILL HAVE 4 MAINS IN THE MAIN ELECTRICAL ROOM AND ONE |
| | MAIN FOR THE FIRE PUMP. PROVIDE LABELING THAT CLEARLY |
| | EXPLAINS THE LOCATION AND NAME OF EACH OF THE MAINS. |
| | NEC 230.2(E) |
| | 8. HDP SHOWS A 400 AMP BREAKER AND FEEDER TO PANEL L, |
| | BUT THE PANEL SCHEDULE FOR PANEL L STATES THAT THE |
| | PANEL IS RATED FOR 225 AMPS. PROVIDE CORRECTION. NEC |
| | 215.2, 408.30, 408.36 |
| | 9. PROVIDE DETAILS OF COMPLIANCE WITH NEC 240.87 FOR |
| | 1200 AMP BREAKER IN MS1. NEC 240.87 |
| | 10. SHEET E-3.02 DOES NOT SHOW THE LOAD CALCULATION FOR |
| | MAIN 1 OF 3. PROVIDE CORRECTION. NEC 220 |
| | 11. PROVIDE GFCI PROTECTION FOR DISHWASHER IN EACH |
| | UNIT. NEC 210.8(D) |
| | 12. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| | EACH PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 |
| | 13. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |