Date Text
2018-06-18 16:35:29 
  
 ****NOTE: COMMENTS WERE UPDATED BECAUSE THEY WERE
 DUPLICATED. 07/09/18 JG>
  
  
  
 NEW 4 STORY APARTMENT BUILDING (R2). BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017).
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
 1- IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
 2- A)SURVEYS NEED THE SURVEYORS SEAL AND SIGNATURE.
 CHAPTER 472 F.S.
 B) PROVIDE SURVEY WITH PROPOSED BUILDING AND SETBACKS.
 SEC. 107.3.5.1 CITY AMENDMENTS.
  
 C)ACCORDING TO THE NEW FLOOD MAPS THAT WENT INTO EFFECT
 ON OCTOBER 5TH 2017, THIS PROPERTY IS LOCATED IN
 EXPOSURE "X" NOT A8. REVISE AS REQUIRED AND PROVIDE
 CURRENT MAP COMMUNITY PANEL NUMBER ALSO. CITY ORDINANCE
 4729-17. REVISE SURVEYOR'S NOTE #5.
  
 4- SHEET A0.04 ARCHITECTURAL PROJECT SPECIFIC NOTES:
 A)PROJECT DATA/CODE REFERENCE INFORMATION SPECIFIES
 CONSTRUCTION TYPE III-B. REVISE INFORMATION ON EXTERIOR
 BEARING WALLS ON SAME PAGE TO SPECIFY 2 HOUR FIRE
 RATING NOT 1 HOUR. TABLE 601 FBC.
  
 B) INFORMATION BELOW "UNIT MAJOR COMPONENT MATRIX"
 REFERENCES 2014 FLORIDA ACCESSIBILITY CODE SEC.
 233.3.1.2. THE CURRENT CODE IS THE 2017 FBC
 ACCESSIBILITY. REVISE AS REQUIRED. CHAPTER 553 F.S.
 NOTE: ALSO REVISE CALCULATION FOR ROLL-IN SHOWER.
 CALCULATION SHALL BE (87X.15)TO REFLECT THE 15% OF
 TOTAL RESIDENTIAL UNITS NOT (87X.12). SEC. 107.2.1 CITY
 AMENDMENTS.
  
 C) PROJECT DATA/CODE REFERENCE INFORMATION SPECIFIES
 FLOOD ZONE A-8. COORDINATE WITH ITEM #2(C) ABOVE FOR
 CORRECT FLOOD ZONE AND REVISE AS REQUIRED. CITY
 ORDINANCE 4729-17.
  
 5- SHEET A0.07 LIFE SAFETY NOTES AND CODE INFORMATION:
 A) BUILDING CODE ANALYSIS ITEM #4 SPECIFIES
 CONSTRUCTION TYPE III-B. REVISE INFORMATION ON EXTERIOR
 BEARING WALLS ON SAME PAGE TO SPECIFY 2 HOUR FIRE
 RATING NOT 1 HOUR.
 ALSO, PROPOSED BUILDING HEIGHT IS NOT CLEAR. 56'-2"
 DOESN'T MATCH BUILDING ELEVATIONS AND WALL SECTIONS.
 REVISE/CLARIFY.
  
 B) BUILDING CODE ANALYSIS ITEM #5 SPECIFIES FBC TABLE
 1005.1. THERE IS NOT TABLE 1005.1. REVISE AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 C) BUILDING CODE ANALYSIS ITEM #6 SPECIFIES FBC TABLE
 1016.1. THERE IS NOT TABLE 1005.1. REVISE AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 D) REVISE BUILDING CODE ANALYSIS ITEM # 9 FOR INTERIOR
 WALL AND CEILING REQUIREMENTS. THERE IS NOT TABLE FBC
 803.9 AND 804.4.1. REVISE AS REQUIRED. SEC. 107.2.1
 CITY AMENDMENTS.
  
 E) REVISE INFORMATION ON ITEM #12 OF BUILDING CODE
 ANALYSIS. THIS PROJECT IS LOCATED IN THE CITY WEST PALM
 BEACH NOT CITY OF MIAMI. SEC. 107.2.1 CITY AMENDMENTS.
  
 6- SHEET A0.08 LIFE SAFETY FLOOR PLAN GROUND LEVEL:
 A) REVISE NUMBER OF OCCUPANTS FOR THE WELLNESS CENTER.
 FOR THE PURPOSE OF OCCUPANT LOAD USE THE EXERCISE ROOMS
 OCCUPANT LOAD FACTOR OF 50SF (GROSS) NOT BUSINESS 100SF
 (GROSS). REVISE AS REQUIRED. SEE TABLE 1004.1.2 FBC AND
 REVISE AS REQUIRED.
  
 B) REVISE NUMBER OF OCCUPANTS FOR THE MULTIPURPOSE
 ROOM. THIS IS NOT BUSINESS OCCUPANCY. FOR THE PURPOSE
 OF OCCUPANT LOAD USE THE ASSEMBLY OPTION THAT BEST
 REFLECTS THE USE OF THIS ROOM. SEE TABLE 1004.1.2 FBC
 AND REVISE AS REQUIRED.
  
 7- SHEET A0.09 LIFE SAFETY FLOOR PLAN TYPICAL LEVEL:
 TRASH ROOM AND TRASH CHUTE NEED TO BE FIRE RATED. SEC.
 713 FBC.
  
 8- SHEET A0.11 ZONING DATA:
 A) BUILDING HEIGHT IS NOT CLEAR. BUILDING HEIGHT SHOWN
 ON THE PROJECT INFO. DOESN'T MATCH HEIGHT SHOWN ON
 EXTERIOR ELEVATIONS AND SECTIONS AND ON PROJECT DATA
 INFORMATION SHOWN ON OTHER SHEETS. REVISE AS REQUIRED
 TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 B) NOTE: PARKING REQUIREMENTS WILL BE REVIEWED AFTER
 ZONING FINAL APPROVAL ON REQUIRED NUMBER OF PARKING
 SPACES. ACCORDING TO FOOTNOTE * AT THE BOTTOM OF
 PROJECT INFO. IT LOOKS LIKE THERE MAY BE A CITY WAIVER
 (40% REDUCTION) ON REQUIRED PARKING SPACE FOR SENIOR
 HOUSING.
  
 C) BUILDING AREA CALCULATION IS NOT CLEAR. WHY SAME
 AREA FOR LEVEL 1 AND LEVELS 2 TO 4. ALSO, COORDINATE
 WITH BUILDING AREA ON OTHER3 SHEETS AND REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS
  
 9- SHEET A1-03 FLOOR PLAN ROOF: SPECIFY LOCATION AND
 SIZE OF ROOF VENTS SPECIFIED ON THE ROOF PLAN GENERAL
 NOTES TO SHOW COMPLIANCE WITH ROOF CROSS VENTILATION
 SEC. 1203.2 FBC.
  
 10-SHEET A3.01 ENLARGED PLANS UNIT TYPE:
 A) KEYED ITEMS ON REFLECTED CEILING PLAN DON'T MATCH
 UNIT KEYNOTES. WHAT'S AW, AV?
 SEC. 107.2.1 CITY AMENDMENTS.
  
 B) KEYED ITEMS ON FINISH PLAN DON'T MATCH UNIT
 KEYNOTES. WHAT'S PT-1, PT-2?
 SEC. 107.2.1 CITY AMENDMENTS.
  
 11- SHEET A3.02 ENLARGED PLANS UNIT TYPE:
 KEYED ITEMS ON FINISH PLAN DON'T MATCH UNIT KEYNOTES.
 WHAT'S PT-1, PT-2?
 SEC. 107.2.1 CITY AMENDMENTS.
  
 12- SHEET A4.01 EXTERIOR ELEVATIONS (NORTH AND EAST):
 A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 ATTACHMENT OF ALL ORNAMENTAL PRECAST CONCRETE BRACKETS.
 SEC. 1601.1 FBC.
  
 B)PROVIDE PROVIDE COMPLETE DETAILS AND SPECIFICATIONS
 FOR THE FOAM BAND SHOWING COMPLIANCE WITH SEC. 2603.5
 FBC.
  
 C) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION AND INSTALLATION OF THE DECORATIVE
 ELEMENTS #09.
 SPECIFY ALL MATERIALS AND FASTENERS. SEC. 106.1.1 FBC.
  
 13- SHEET A4.12 ENLARGED PLANS AND INT. ELEVATIONS
 BATHROOM: PROVIDE DETAILS AND SPECIFICATIONS FOR
 REINFORCING AROUND TOILETS, TUBS AND SHOWERS OF ALL
 BATHROOMS AS REQUIRED BY REQUIREMENT #6 OF FAIR HOUSING
 ACT.
  
 14-SHEET A4.13 ENLARGED PLANS AND INT. ELEV. KITCHEN
 TYP. UNITS: CLARIFY WHY THE DIMENSION BETWEEN BOTTOM
 KITCHEN CABINETS AND TOP KITCHEN CABINETS ARE DIFFERENT
 ON CABINETS MILLWORK DETAIL #07 AND KITCHEN ELEVATIONS
 #08 AND #09?. SEC. 107.2.1 CITY AMENDMENTS. ALSO,
 DIMENSION OF TOP CABINETS IS DIFFERENT. CLARIFY.
 NOTE: SAME COMMENT APPLIES TO SHEET A4-14.
  
 15- SHEET A5-02 WALL SECTIONS:
 A) TYPE III BUILDINGS DON'T ALLOW NON-COMBUSTIBLE
 MATERIALS ON EXTERIOR WALL. REVISE WALL SECTION KEYNOTE
 #16. FIRE RETARDANT WOOD MAY BE USED. SEC. 602.3 FBC.
 SAME APPLIES TO SHEET A5-03.
  
 B) REVISE WALL SECTION KEYNOTE #21 AND #22. DESIGNER OF
 RECORD TO PROVIDE DETAILS AND SPECIFICATIONS FOR SOFFIT
 METAL STUD FRAMING AND FOR DRYWALL SHEATHING. THIS IS
 NOT DONE BY THE METAL STUD MANUFACTURER. SEC. 1601.1
 FBC. SAME APPLIES TO SHEET A5-03.
  
 C) PROVIDE DETAIL AND SPECIFICATIONS FOR ROOF
 INSULATION ON PITCHED ROOF. SEC. C103.2 FBC-ENERGY
 CONSERVATION. SAME APPLIES TO SHEET A5-03.
  
 D) CLARIFY WALL SECTION KEYNOTE #13 AND #19. FIRE
 RETARDED WOOD? SEC. 107.2.1 CITY AMENDMENTS. SAME
 APPLIES TO SHEET A5-03.
  
 16- SHEET A6.01- ENLARGED PLANS AND SECTION STAIR NO
 01: BOTTOM EXTENSION AT STAIRS OF FLOOR PLAN GROUND
 LEVEL NEED TO BE COMPLY WITH SEC. 505.10.3
 FBC-ACCESSIBILITY. EXTENSION ON BOTH SIDES OF STAIRS
 NEED TO COMPLY. THEY NEED TO EXTEND AT THE SLOPE OF THE
 STAIR. ONE OF THEM IS TURNING. THIS IS ONLY ALLOWED
 WHEN CONNECTING TO ANOTHER HANDRAIL. SAME APPLIES TO
 SHEET A6-02.
  
 17- SHEET A6.03 - ENLARGED PLANS AND SECTION ELEVATOR:
 A) REVISE ELEVATOR GENERAL NOTE #1. REVISE THE STANDARD
 REFERENCED. SEE CHAPTER 35 FB FOR CORRECT ASME SECTION
 AND CURRENT EDITION AND REVISE AS REQUIRED.
  
 B) UPDATE ALL ELEVATOR GENERAL NOTES. PROVIDE CORRECT
 CODE SECTIONS REFERENCING THE CURRENT 2017
 FBC-ACCESSIBILITY.
  
 C) PROVIDE SIZE OF ELEVATOR CARS SHOWING COMPLIANCE
 WITH SEC. 3002.4 FBC FOR AMBULANCE STRETCHER.
  
 18- WINDOW TAG "B" ON WINDOW SCHEDULE ON SHEET A8.11
 EXTERIOR OPENING SCHEDULES STATES THAT THIS WINDOW IS
 "NOT USED".
 BUT ARCHITECTURAL FLOOR PLANS SHOW WINDOW "B" ON UNIT
 TYPE "A" LOCATED ON NORTH EAST CORNER. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 19- DOOR TYPES SHOWN ON THE DOOR TYPE ELEVATIONS DON'T
 MATCH DOOR TYPE SHOWN ON THE DOOR SCHEDULES AND FLOOR
 PLANS. REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 20- PROVIDE 2 HOUR FIRE RATED ASSEMBLY DETAILS AND
 SPECIFICATIONS FOR POURED CONCRETE SHEARWALLS AT
 STAIRWAYS AND ELEVATOR SHAFT. SEC. 713.4 FBC. DETAILS
 PROVIDED ON SHEET A8.01 IS FOR CONCRETE BLOCK WALLS
 ONLY.
  
 21- SHEET A9.02-STAIR AND RAILING DETAILS: CLARIFY
 DETAIL 09 TYPICAL HANDRAIL DETAIL AT LOWER LANDING. IT
 DOESN'T SEEM TO COMPLY WITH SEC. 505.10.3
 FBC-ACCESSIBILITY. THE HANDRAIL NEEDS TO RETURN TO THE
 WALL, GUARD, OR LANDING SURFACE.
  
  
 22- PROVIDE COMPLETE DETAIL AND SPECS SHOWING HOW THE
 WOOD TRUSS CONNECTOR #1 SIMPSON META16 IS INSTALLED. IT
 MAY NOT SEEM TO WORK BASED ON THE PROPOSED
 INSTALLATION. SEC. 107.2.1 CITY AMENDMENTS.
  
 23- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 A)FLAT ROOF SINGLE PLY ROOFING NOA 15-0203.23
 SUBMITTED. CLEARLY MARK WHICH APPROVED ASSEMBLY IS
 GOING TO BE INSTALLED. NOTE: IF THE SELECTED ASSEMBLY
 DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES,
 THEN SIGNED AND SEALED RAS 117 CALCULATIONS ARE
 REQUIRED.
  
 B)CONCRETE ROOF TILE NOA 16-0112.07: DESIGNER OF RECORD
 TO SPECIFY ROOF TILE FASTENING METHOD AS REQUIRED BY
 SEC. 107.2.1.1 CITY AMENDMENTS. IF SPECIFYING TILE
 ADHESIVE, THEN PROVIDE PRODUCT APPROVAL FOR LISTED
 ADHESIVE.
  
 C) ALUMINUM STOREFRONT SYSTEM NOA 17-1114.02 SUBMITTED.
 CLEARLY SPECIFY MULLION AND WINDOW SIZES. SEC. 1601.1
 FBC.
  
 D) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 E) CHUTE ALUMINUM CAP AS SHOWN ON PLANS.
  
 24-- DESIGNER OF RECORD TO REVIEW AND APPROVE IN
 WRITING (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS
 AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 25- PROVIDE COMPLETE TRUSS PACKAGE SUBMITTAL REVIEWED
 BY THE DESIGNER OF RECORD. SEC. 107.3.4.1 CITY
 AMENDMENTS.
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 26- ALL ENGINEER DOCUMENTS THAT ARE SUBMITTED FOR
 PUBLIC RECORDS NEED TO HAVE ORIGINAL SEAL AND SIGNATURE
 AS REQUIRED BY CHAPTER 471 F.S. WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS. PROVIDE HARD COPIES WITH
 ORIGINAL SEAL AND SIGNATURE FOR ALL DOCUMENTS THAT WERE
 NOT SUBMITTED WITH DIGITAL SIGNATURE.
  
 27- PROVIDE COMPLETE ENGINEERED DETAILS AND
 SPECIFICATIONS FOR THE CONSTRUCTION OF ALL THE ENTRY
 CANOPIES. SEC. 1601.1 FBC.
  
 28- TRASH ROOM DOOR TYPE ELEVATION TYPE I SHOWN ON
 SHEET A8.21 FOR DOOR #1220 DOESN'T MATCH SIZE SHOWN ON
 THE DOOR SCHEDULE. ALSO. NOA 10-1014.05 LISTED N THE
 DOOR ELEVATION IS EXPIRED. REVISE AS REQUIRED TO MATCH.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 29- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 A)FLAT ROOF SINGLE PLY ROOFING NOA 15-0203.23
 SUBMITTED. CLEARLY MARK WHICH APPROVED ASSEMBLY IS
 GOING TO BE INSTALLED. NOTE: IF THE SELECTED ASSEMBLY
 DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES,
 THEN SIGNED AND SEALED RAS 117 CALCULATIONS ARE
 REQUIRED.
  
 B)CONCRETE ROOF TILE NOA 16-0112.07: DESIGNER OF RECORD
 TO SPECIFY ROOF TILE FASTENING METHOD AS REQUIRED BY
 SEC. 107.2.1.1 CITY AMENDMENTS. IF SPECIFYING TILE
 ADHESIVE, THEN PROVIDE PRODUCT APPROVAL FOR LISTED
 ADHESIVE.
  
 C) ALUMINUM STOREFRONT SYSTEM NOA 17-1114.02 SUBMITTED.
 CLEARLY SPECIFY MULLION AND WINDOW SIZES. SEC. 1601.1
 FBC.
  
 D) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 E) ROOF VENTS FOR CONCRETE ROOF TILE INSTALLATION AND
 CLEARLY SPECIFY LOCATION ON ROOF.
  
 F)ROOF ATTIC ACCESS DOORS SHOWN ON ROOF PLAN.
  
 G) FIXED WINDOWS AS SHOWN ON PLANS.
  
 H) CORRELATE EACH DOOR NOA SUBMITTED WITH THE PROPOSED
 LOCATION/ROOM.
  
 30- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 31- PROVIDE COMPLETE TRUSS PACKAGE SUBMITTAL REVIEWED
 BY THE DESIGNER OF RECORD. SEC. 107.3.4.1 CITY
 AMENDMENTS.
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 32- ALL ENGINEER DOCUMENTS THAT ARE SUBMITTED FOR
 PUBLIC RECORDS NEED TO HAVE ORIGINAL SEAL AND SIGNATURE
 AS REQUIRED BY CHAPTER 471 F.S. WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS. PROVIDE HARD COPIES WITH
 ORIGINAL SEAL AND SIGNATURE FOR ALL DOCUMENTS THAT WERE
 NOT SUBMITTED WITH DIGITAL SIGNATURE.
  
 33- PROVIDE COMPLETE ENGINEERED DETAILS AND
 SPECIFICATIONS FOR THE CONSTRUCTION OF ALL THE ENTRY
 CANOPIES. SEC. 1601.1 FBC.
  
 34- FLOORING UNDERLAYMENT (NOTE: THIS MAY BE SUBMITTED
 LATER AS A DEFERRED SUBMITTAL).
 1- SOUND INSULATION MATERIAL:
 A) PROVIDE 2 COPIES OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 6TH EDITION
 (2017).
 B) PROVIDE 2 COPIES OF THE SOUND TRANSMISSION CLASS
 (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90 AS
 REQUIRED BY SEC. 1207.2 OF FBC 6TH EDITION (2017).
 C) PROVIDE 2 COPIES OF THE IMPACT INSULATION CLASS
 (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492 AS
 REQUIRED BY SEC. 1207.3 OF FBC 6TH EDITION (2017).
  
 35- PROVIDE SITE PLAN SHOWING COMPLIANCE WITH THE
 ACCESSIBLE ROUTE FROM THE PUBLIC STREET AS REQUIRED BY
 SEC. 206.2.1 FBC ACCESSIBILITY.
  
 360- VALUATION DECLARED IN THE PERMIT APPLICATION IS
 LOW. SEC. 109.3 CITY AMENDMENTS. UPDATE VALUATION.
 SEC. 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 37- SEC. 110.7 CITY AMENDMENTS: SHORING. FOR THRESHOLD
 BUILDINGS, SHORING AND ASSOCIATED FORMWORK OR FALSEWORK
 SHALL BE
 DESIGNED AND INSPECTED BY A FLORIDA LICENSED
 PROFESSIONAL ENGINEER, EMPLOYED BY THE PERMIT HOLDER
 OR SUBCONTRACTOR, PRIOR TO ANY REQUIRED MANDATORY
 INSPECTIONS BY THE THRESHOLD BUILDING INSPECTOR. ALL
 SHORING AND RESHORING PROCEDURES, PLANS AND DETAILS
 SHALL BE SUBMITTED TO THE ENFORCEMENT AGENCY
 FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 38- SEC. 110.8 CITY AMENDMENTS: THRESHOLD BUILDING.
  
 CITY AMENDMENTS SEC. 110.8.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM STRUCTURAL
 INSPECTIONS ON A THRESHOLD BUILDING PURSUANT TO A
 STRUCTURAL INSPECTION PLAN PREPARED BY THE
 ENGINEER OR ARCHITECT OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A
 THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLANS IS TO PROVIDE SPECIFIC
 INSPECTION PROCEDURES AND SCHEDULES SO THAT THE
 BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS. THE SPECIAL
 INSPECTOR MAY NOT SERVE AS A
 SURROGATE IN CARRYING OUT THE RESPONSIBILITIES OF THE
 BUILDING OFFICIAL, THE ARCHITECT OR THE
 ENGINEER OF RECORD. THE CONTRACTOR'S CONTRACTUAL OR
 STATUTORY OBLIGATIONS ARE NOT RELIEVED BY
 ANY ACTION OF THE SPECIAL INSPECTOR.
  
 NOTE: SPECIAL INSPECTOR IS REQUIRED. CONTACT JULIO
 GOMEZ (561)805-6712 FOR MORE INFORMATION REGARDING
 SPECIAL INSPECTOR REQUIREMENTS AND APPROVAL. SEC. 110.8
 CITY AMENDMENTS
  
 CITY AMENDMENT SEC. 110.8.4.4 ALL PLANS FOR THE
 BUILDING WHICH ARE REQUIRED TO BE SIGNED AND SEALED
 BY THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A
 STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE
 APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE
 FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633.
 FLORIDA STATUTES.
  
 39-ART IN PUBLIC PLACES
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE
 DEVELOPMENT.
 (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND
 THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL
 PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW
 CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN
 EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS
 WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED
 CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES
 REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED
 SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF
 THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW
 CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS.
  
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 40- PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 41- NOTE: CLARIFY IF THIS BUILDING IS GOING TO BE USED
 AS AN ASSISTED LIVING FACILITY. SEE ELECTRICAL
 COMMENTS. PLAN REVIEW WAS DONE BASED ON AN RESIDENTIAL
 R2 OCCUPANCY. ASSISTED LIVING FACILITIES ARE REVIEWED
 UNDER THE INSTITUTIONAL OCCUPANCY AND CODE REQUIREMENTS
 DIFFER. CLEARLY STATE ON PLANS PROPOSED USE. SEC. 301.1
 FBC.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  