| 2018-06-29 15:28:27 | 06/29/2018 2ND PLUMBING REVIEW**DENIED** |
| | |
| | COMMENTS SUBMITTED BY PLUMBING CONTRACTOR MUST BE |
| | PLACED ONTO PLAN. ALSO SUBMITTAL DOCUMENTS ARE NOT |
| | PERMITTED TO BE IN PENCIL. FBC 107.3.5 |
| | |
| | 1) **CHANGES MUST BE MADE ON PLAN BY ARCHITECT OF |
| | RECORD**SANITARY ISOMETRIC IS SHOWING BATH #2 HAS 2 WET |
| | VENTED FIXTURES PASSED THE DRY VENT. ONLY 1 WET VENTED |
| | FIXTURE IS PERMITTED BEYOND THE DRY VENT. FBC R |
| | P3108.2.1 |
| | |
| | 2) **CHANGES MUST BE MADE ON PLAN BY ARCHITECT OF |
| | RECORD**PLUMBING NOTES LIST NEW COLD WATER PIPING TO BE |
| | PVC SCH 40. PVC IS ONLY PERMITTED OUTSIDE, UNDERGROUND |
| | AND SHALL TERMINATE AT OR BEFOR THE FULL OPEN VALVE AT |
| | THE ENTRANCE OF THE HOME. WATER DISTRIBUTION PIPING ( |
| | INSIDE OF HOME) SHALL BE OF 1 OF THE MATERIALS OF |
| | PIPING LISTED IN TABLE FBC R P 2906.5 |
| | |
| | 3) **CHANGES MUST BE MADE ON PLAN BY ARCHITECT OF |
| | RECORD**PLUMBING NOTES LIST ALL SANITARY PIPING TO BE |
| | 1/8" PER FOOT. NOT ALL PIPE SIZES ARE PERMITTED TO HAVE |
| | A MIN 1/8" PITCH AS IN TABLE FBC R P3005.4.2 PLEASE ADD |
| | COMMENT IN REGRADS TO SMALLER SIZES OR REMOVE NOTES ALL |
| | TOGETHER AS THIS IS A GENERAL MIN CODE REQUIREMENT THAT |
| | EVER PLUMBER SHOULD KNOW. |
| | |
| | 4) NO RESPONCE**PROVIDE SPEC/ INSTALLATION MANUAL FOR |
| | THE WATER HEATER. ALSO PLEASE ADD NOTE TO THE WATER |
| | HEATER ON SHT. E1.0 AND SHT. A1.0 SHOWING MIN E.F WILL |
| | BE .97 E.F. PER YOUR R405-2017 FORM LIST THE WATER |
| | HEATER AS .97 E.F AND IS ABOVE THE MIN .95 E.F BUT |
| | SHOWING AS NEEDED FOR YOUR COMPLIANCE WITH THE |
| | R405-2017 FORM. |
| | |
| | 5) **CHANGES MUST BE MADE ON PLAN BY ARCHITECT OF |
| | RECORD**PROVIDE RELIEF LINE AND PAN DRAIN DISCHARGE |
| | PIPING DETAIL SHOW HOW YOU ARE COMPLYING WITH FBC R |
| | P2804.6.1. RELIEF LINE SHALL DISCHARGE INTO THE ROOM OF |
| | THE WATER HEATER AND ARE NOT PERMITTED TO BE TRAPPED. |
| | |
| | |
| | TIM HUNT |
| | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER |