| 2018-06-06 15:54:32 | 06/06/2018 1ST PLUMBING REVIEW**DENIED** |
| | |
| | 1) SANITARY ISOMETRIC IS SHOWING BATH #2 HAS 2 WET |
| | VENTED FIXTURES PASSED THE DRY VENT. ONLY 1 WET VENTED |
| | FIXTURE IS PERMITTED BEYOND THE DRY VENT. FBC R |
| | P3108.2.1 |
| | |
| | 2) PLUMBING NOTES LIST NEW COLD WATER PIPING TO BE PVC |
| | SCH 40. PVC IS ONLY PERMITTED OUTSIDE, UNDERGROUND AND |
| | SHALL TERMINATE AT OR BEFOR THE FULL OPEN VALVE AT THE |
| | ENTRANCE OF THE HOME. WATER DISTRIBUTION PIPING ( |
| | INSIDE OF HOME) SHALL BE OF 1 OF THE MATERIALS OF |
| | PIPING LISTED IN TABLE FBC R P 2906.5 |
| | |
| | 3) PLUMBING NOTES LIST ALL SANITARY PIPING TO BE 1/8" |
| | PER FOOT. NOT ALL PIPE SIZES ARE PERMITTED TO HAVE A |
| | MIN 1/8" PITCH AS IN TABLE FBC R P3005.4.2 PLEASE ADD |
| | COMMENT IN REGRADS TO SMALLER SIZES OR REMOVE NOTES ALL |
| | TOGETHER AS THIS IS A GENERAL MIN CODE REQUIREMENT THAT |
| | EVER PLUMBER SHOULD KNOW. |
| | |
| | 4) PROVIDE SPEC/ INSTALLATION MANUAL FOR THE WATER |
| | HEATER. ALSO PLEASE ADD NOTE TO THE WATER HEATER ON |
| | SHT. E1.0 AND SHT. A1.0 SHOWING MIN E.F WILL BE .97 |
| | E.F. PER YOUR R405-2017 FORM LIST THE WATER HEATER AS |
| | .97 E.F AND IS ABOVE THE MIN .95 E.F BUT SHOWING AS |
| | NEEDED FOR YOUR COMPLIANCE WITH THE R405-2017 FORM. |
| | |
| | 5) PROVIDE RELIEF LINE AND PAN DRAIN DISCHARGE PIPING |
| | DETAIL SHOW HOW YOU ARE COMPLYING WITH FBC R P2804.6.1 |
| | |
| | |
| | TIM HUNT |
| | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER |