2018-10-02 08:37:05****CORRECTIONS****
 W.P.B. PERMIT: 18050348
 3RD REVIEW: OCTOBER 2, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. OK
  
 2. NO COMMENT RESPONSE SHEET PROVIDED SO I CAN?T SEE
 HOW A DRAINAGE PLAN IS BEING IMPLEMENTED TO MAINTAIN
 DRAINAGE WITH THE SITE.
 PLEASE PROVIDE SITE DRAINAGE PLAN ACCORDING TO THE
 FOLLOWING CODE REFERENCES-[FBC AMENDED 107.5][FBC
 110.9][FBC R401.3]
  
 3. FBC 110.9, PROVIDE A DETAIL TO SHOW HOW ADJACENT
 PROPERTIES WILL BE PROTECTED (SILT FENCE).
  
 3. ADDITIONAL COMMENT-A SILT FENCE DETAIL CAN BE FOUND
 AT-
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 4. OK
  
 5. FBC R 311.2, REVISE PLAN TO SHOW ENTRY DOOR WITH
 MINIMUM 32" CLEAR WIDTH.
  
 6. FBC 107, REVISE PLAN TO INCLUDE ALL DOOR SIZES
 (EXAMPLE; ENTRY DOOR, WIC).
  
 7. FBC 107, FBC R 301, REVISE PLAN TO SHOW ALL WINDOW
 SIZES (EXAMPLE; ENTRY DOOR SIDELITE).
  
 8. A1GH, DOOR FROM GARAGE TO GUEST HOUSE, REVISE PLAN
 TO SHOW COMPLIANCE WITH FBC R 303.5.1.
  
 5-8. ADDITIONAL COMMENT-THESE CAN ALL BE ADDRESSED BY
 ADDING A WINDOW AND DOOR SCHEDULE.
  
 9. A1ADD, A1GH, WALL BETWEEN GARAGE AND RESIDENCE,
 CLARIFY CONSTRUCTION AND INSULATION, FBC R 302.6. NOTE
 THAT INSULATION IS SHOWN GRAPHICALLY ON A PORTION OF
 THE WALL ON A1ADD; NOT CLEAR WHY THIS ISN'T CONTINUOUS
 ON ALL GARAGE WALLS SEPARATING GARAGE FROM RESIDENCE.
  
 9. ADDITIONAL COMMENT-THIS COMMENT WAS BEACAUSE THERE
 IS INSULATION HATCH AT GARAGE WALL, BUT THE HATCH ISN?T
 APPLIED ALONG THE WHOLE GARAGE /HOUSE DIVIDING WALL.
 PLEASE SHOW THE INSULATION HATCHING TO SHOW CONTINUOUS
 THERMAL BARRIER.
 FOR CONSISTENCY CAN THE HATCH BE APPLIED TO BOTH NEW
 GARAGES, OR SHOW WALL TYPE DETAIL COMMON TO GARAGE
 SEPARATION.
  
 10-12. OK
  
 NEW COMMENTS FROM GUEST HOUSE REMOVAL:
  
 13. CONSOLIDATE THE AREA TABULATIONS.
 SHOW EXISTING UNDER AIR AND EXISTING TOTAL (3301 UNDER
 AIR AND 4298 TOTAL ACCORDING TO PROPERTY APPRAISERS)
 NEW ADDITION UNDER AIR AND NEW TOTAL.
 NEW TOTAL UNDER AIR AND NEW TOTAL SQ. FOOTAGE.
 THE NEW TABLE SHOULD REPLACE THE TABLES ON S-1, A-1 ADD
 AND A1 ADD-W.
  
 14. CONSOLIDATE THE ENERGY CALCULATIONS. PUT ALL AREA,
 INCLUDING THE NEW SPACE CONNECTED THE PREVIOUS LAYOUTS,
 INTO ONE ENERGY CALCULATION SUBMITTAL.
  
 15. SHEET C-1 REMOVE THE WORD GUEST HOUSE FROM TITLE
 BLOCK, MAIN TITLE AND DRAWING INDEX.
  
 16. SHEET A-1 PROVIDE NEW SHEET W/O GUEST HOUSE IN THE
 TITLE BLOCK AND THE PBC STAMP FOR IMPACT WOULD NO
 LONGER BE VALID FOR THIS PROJECT. (SEE IMPACT REVIEW
 FOR COMMENTS ON IMPACT).
  
 17. SHEET A-4 REMOVE GUEST HOUSE FROM TITLE BLOCK.
  
 18. [FBC R302.10]PROVIDE CUT SHEET FOR ICYNENE(ICC-ES
 REPORT OR EQUAL) WITH THE TYPE SELECTED TO ESTABLISH
 THICKNESS NEEDED TO MEET REQUIRED R-VALUE, FLAME SPREAD
 INDEX AND SMOKE DEVELOPED INDEX.
 ICYNENE REQUIRES THERMAL BARRIER FROM ATTIC. IF THERE
 IS MECHANICAL EQUIPMENT IN THE SPACE THAN IT REQUIRES
 IGNITION BARRIER.
  
 19. [FBC AMENDED 107.3.4.1]PROVIDE PRODUCT APPROVALS
 FOR ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM
 DEFERED.
 10/4/18 CUSTOMER REQUESTED DEFERAL AND R-STOP IS
 CHANGED TO "N" STATUS TO INDICATE THAT ROOFER WILL
 PROVIDE SUBMITTAL UNDER ROOFING SUB PERMIT.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  