Plan Review Notes
Plan Review Notes For Permit 18050348
Permit Number 18050348
Review Stop P
Sequence Number 2
Notes
Date Text
2018-08-30 16:01:51PERMIT 18050348
  
 2ND REVIEW: FBC 2017 6TH EDITION
 DENIED
  
 PLUMBING REVIEW
  
 1. PLAN SHEET A-5; ADDITION PLUMBING RISER DIAGRAM
 NOTATES BAR (BAR SK) AT LOCATION THAT IS INDICATED ON
 A-1 ADD TO BE THE KITCHEN SINK. PLEASE CLARIFY.
 2. SCOPE OF WORK FOR ADDITION AND GUEST HOUSE PLUMBING
 CALLS FOR SUPPLY AND INSTALLATION OF TANKLESS GAS WATER
 HEATERS. LOCATE ON THE PLANS.
 3. PLAN SHEET A-5 ADDITION PLUMBING RISER DIAGRAM;
 PROVIDE SIZE ON FIXTURE BRANCH TO LAUNDRY FIXTURES
 4. THERE IS NO GAS INDICATED ON THE PLANS.
  A. A GAS SUB PERMIT WILL BE REQUIRED.
  B. SPECS FOR UNIT WILL BE REQUIRED.
  C. CALCULATIONS AND PIPING TYPE/MATERIAL FOR PIPING
 WILL BE REQUIRED.
  D. GAS PIPING DIAGRAM WILL BE REQUIRED TO INCLUDE
 DEVELOPED LENGTHS WILL BE REQUIRED.
  E. COMBUSTION AIR AND EXHAUST VENT AND ROUTING OF SAME
 WILL BE REQUIRED FOR GAS WATER HEATERS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711