| 2018-06-07 09:32:23 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (BOTH |
| | COPIES) IS REQUIRED TO BEAR THE NAME AND BE SIGNED AND |
| | SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. |
| | PROVIDE CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481 |
| | 2. THE NEC SPECIFIED FOR DESIGN IS NOT THE CURRENT |
| | CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE CURRENT |
| | CODES ABOVE) |
| | 3. PROVIDE LOAD CALCULATION FOR 400 AMP SERVICE, |
| | INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF |
| | SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE |
| | E3602.2 |
| | 4. NOTE ON PLAN FOR AFCI COMPLIANCE IS NOT ACCURATE. |
| | ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, |
| | 15- AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY |
| | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, |
| | DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| | SHALL BE AFCI PROTECTED. PROVIDE CORRECTION. NEC |
| | 210.12; FBC RE E3902.16 |
| | 5. PROVIDE BLOCK NOTE THAT THE GENERATOR REQUIRES A |
| | SEPARATE PERMIT. WPB FBC 105.1, 107.2.1 |
| | 6. PROVIDE ACCURATE RISER DIAGRAM. PLAN STATES THAT A |
| | GENERATOR WILL BE INSTALLED, BUT NO TRANSFER SWITCHES |
| | ARE SHOWN. ALSO PROVIDE WIRE SIZE FOR FEEDERS AND |
| | GROUNDING ELECTRODE CONDUCTORS TO CONFIRM CODE |
| | COMPLIANCE. NEC 215.5, 230, 250.50, 250.94, 408.30; FBC |
| | RE E3706.1, E3608.1, E3609.3; WPB FBC 107.2.1 |
| | 7. GFCI PROTECTION IS REQUIRED FOR ALL OUTLETS IN |
| | GARAGE, INCLUDING GARAGE DOOR OPENERS AND |
| | REFRIGERATORS. PROVIDE CORRECTION. NEC 210.8; FBC RE |
| | E3902.2 |
| | 8. RECEPTACLES IN STORAGE AREAS REQUIRE GFCI |
| | PROTECTION. PROVIDE CORRECTION. NEC 210.8; FBC RE |
| | E3902.2 |
| | 9. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C |
| | EQUIPMENT WITHIN 25 FEET OF THE EQUIPMENT PER CODE, |
| | INCLUDING THE MINI-SPLIT UNITS. NEC 210.63; FBC RE |
| | E3901.12 |
| | 10. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED |
| | PER CODE. SHOW ON PLAN ALL EXISTING ALARMS. INCLUDE |
| | MAIN HOUSE EXISTING FLOOR PLAN. IF NONE ARE EXISTING OR |
| | NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC RE R314.3, |
| | R315.1; WPB FBC 107.2.1 |
| | 11. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC |
| | 210.8(D); FBC RE E3902.10 |
| | 12. PROVIDE GFCI PROTECTED OUTLET ON THE KITCHEN |
| | PENINSULA AT A LOCATION WHERE THERE IS NOT THE 12 INCH |
| | COUNTER TOP OVERHANG.. NEC 210.8, 210.52(C)(3); FBC RE |
| | E3901.4.3, 3901.4.5 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |
| | |