| 2018-06-18 18:07:01 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR |
| | PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINAL |
| | (SOILS REPORTS), FS471, FAC61G15-23.002. |
| | |
| | 2. FBC 107.2.5, DRAINAGE PLAN IS REQUIRED. SEE ALSO FBC |
| | 110.9: |
| | |
| | 110.9 IMPACT OF CONSTRUCTION. ALL CONSTRUCTION ACTIVITY |
| | REGULATED BY THIS CODE SHALL BE PERFORMED |
| | IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION |
| | OF ADJACENT PROPERTY, UNLESS SUCH |
| | ACTIVITY IS PERMITTED TO AFFECT SAID PROPERTY PURSUANT |
| | TO A CONSENT GRANTED BY THE APPLICABLE |
| | PROPERTY OWNER, UNDER TERMS OR CONDITIONS AGREEABLE TO |
| | THE APPLICABLE PROPERTY OWNER. THIS |
| | INCLUDES, BUT IS NOT LIMITED TO, THE CONTROL OF DUST, |
| | NOISE, WATER OR DRAINAGE RUN-OFFS, DEBRIS, |
| | AND THE STORAGE OF CONSTRUCTION MATERIALS. NEW |
| | CONSTRUCTION ACTIVITY SHALL NOT ADVERSELY |
| | IMPACT LEGAL HISTORIC SURFACE WATER DRAINAGE FLOWS |
| | SERVING ADJACENT PROPERTIES, AND MAY |
| | REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE |
| | POSITIVE DRAINAGE PATTERNS OF THE AFFECTED SITES. |
| | ACCORDINGLY, DEVELOPERS, CONTRACTORS AND |
| | OWNERS OF ALL NEW RESIDENTIAL DEVELOPMENT, INCLUDING |
| | ADDITIONS, POOLS, PATIOS, DRIVEWAYS, DECKS |
| | OR SIMILAR ITEMS, ON EXISTING PROPERTIES RESULTING IN A |
| | SIGNIFICANT DECREASE OF PERMEABLE LAND |
| | AREA ON ANY PARCEL OR HAS ALTERED THE DRAINAGE FLOW ON |
| | THE DEVELOPED PROPERTY SHALL, AS A |
| | PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| | DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE |
| | WITH THIS PARAGRAPH. UPON COMPLETION OF THE |
| | IMPROVEMENT, A CERTIFICATION FROM A LICENSED |
| | PROFESSIONAL SHALL BE SUBMITTED TO THE INSPECTOR IN |
| | ORDER TO RECEIVE APPROVAL OF THE FINAL |
| | INSPECTION. |
| | |
| | 3. FBC 110.9, PROVIDE A DETAIL TO SHOW HOW ADJACENT |
| | PROPERTIES WILL BE PROTECTED (SILT FENCE). |
| | |
| | 4. FBC R 314, R 315, NO SMOKE/CO ALARMS SHOWN FOR HOUSE |
| | ADDITION OR EXISTING HOUSE, SMOKE ALARM ONLY SHOWN FOR |
| | GUEST HOUSE, REVISE. |
| | |
| | 5. FBC R 311.2, REVISE PLAN TO SHOW ENTRY DOOR WITH |
| | MINIMUM 32" CLEAR WIDTH. |
| | |
| | 6. FBC 107, REVISE PLAN TO INCLUDE ALL DOOR SIZES |
| | (EXAMPLE; ENTRY DOOR, WIC). |
| | |
| | 7. FBC 107, FBC R 301, REVISE PLAN TO SHOW ALL WINDOW |
| | SIZES (EXAMPLE; ENTRY DOOR SIDELITE). |
| | |
| | 8. A1GH, DOOR FROM GARAGE TO GUEST HOUSE, REVISE PLAN |
| | TO SHOW COMPLIANCE WITH FBC R 303.5.1. |
| | |
| | 9. A1ADD, A1GH, WALL BETWEEN GARAGE AND RESIDENCE, |
| | CLARIFY CONSTRUCTION AND INSULATION, FBC R 302.6. NOTE |
| | THAT INSULATION IS SHOWN GRAPHICALLY ON A PORTION OF |
| | THE WALL ON A1ADD; NOT CLEAR WHY THIS ISN'T CONTINUOUS |
| | ON ALL GARAGE WALLS SEPARATING GARAGE FROM RESIDENCE. |
| | |
| | 10. A3ADD, IT APPEARS SOME CONNECTORS ARE NOT |
| | SPECIFIED. SEE COURTYARD, BEDROOM A, CHECK ALL. |
| | |
| | 11. FBC 107, PRODUCT APPROVALS ARE TO BE REVIEWED BY |
| | DESIGNER OF RECORD. |
| | |
| | 12. WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED |
| | SETS OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". |
| | |
| | 13. PROVIDE VALUE FOR THE FOLLOWING; SEPARATE PERMITS |
| | ARE REQUIRED: |
| | |
| | ADDITION |
| | GUEST HOUSE |
| | GENERATOR |
| | |
| | |
| | |