Plan Review Notes
Plan Review Notes For Permit 18050330
Permit Number 18050330
Review Stop P
Sequence Number 1
Notes
Date Text
2018-06-06 13:50:161ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE SINKS IN ROOMS 902 AND 915 SHALL COMPLY WITH FBC
 ACC 212.3 , 606.2, 606.3
  
 2. PLEASE PROVIDE COST BREAK DOWN TO SHOW COMPLIANCE
 WITH FBC ACC
 202.4.1 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 3. SHT. A-1 UNDER PLUMBING FIXTURE IT LIST A DRINKING
 FOUNTAIN BUT NONE IS SHOWN ON THE PLAN PLEASE CLARIFY.
 PER WPB AMEND TO FBC 107.2.1
  
 4. SHT. A-3 PLAN NOTE 02 LIST A HI LO WATER FOUNTAIN
 BUT NONE IS SHOWN ON THE PLAN PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 5. IS THERE AN EXISTING HOT WATER RECIRCULATION LINE.
 THE HOT WATER ON THE NEW SINKS SHALL COMPLY WITH FBC PL
 607.2
  
 6. EACH DROP ON THE WATER SYSTEM SHALL HAVE A SHUT OFF
 VALVE WITH ACCESS TO IT. PER FBC PL 606.1 (5)
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  