2018-06-06 05:56:3406/06/2018 1ST PLUMBING REVIEW**DENIED**
  
 1) PROVIDE LEVEL OF ALTERATION AND TOTAL PERCENT OF
 WORK AREA. FBC R-EXISTING 501.2
  
 2) PROVIDE THE SPECIFICATIONS/ INSTALLATION MANUALS
 ALONG WITH FLOW CHARTS FOR THE TANKLESS WATER HEATERS.
 FBC 107.2.1
  
 3) PROVIDE AN EXISTING FLOOR PLAN LAY OUT. FBC 107.2.1
  
 4) PROVIDE WALL DIMENSION FOR EACH ROOM TO SHOW THE
 MINIMAL CLEARANCES FOR THE PLUMBING FIXTURES WILL
 COMPLY. FBC R P2705.1
  
 5) IS THE COPPER PIPING SHOWN AS EXISTING IN THE LIVING
 ROOM THE ONLY EXISTING WATER PIPING THAT WILL BE REUSED
 IN THE NEW SYSTEM? FBC 107.2.1
  
 6) YOUR SANITARY ISOMETRIC IS SHOWING AS A WASTE & VENT
 IN BATH #1 AND GUEST BATH. TOILETS AND GARBAGE
 DISPOSALS ARE NOT PERMITTED TO DISCHARGE INTO THIS TYPE
 OF SYSTEM PER FBC R P3111.1. PLEASE SHOW HOW YOU INTENT
 TO VENT THESE TWO BATHROOM GROUPS.
  
  
 TIM HUNT
  PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
  CITY OF WEST PALM BEACH DEVELOPMENT SERVICES
 DEPARTMENT
  BUILDING DIVISION
  561-805-6695
  [email protected]
  