| Plan Review Notes For Permit 18050326 |
| Permit Number |
18050326 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-06-06 05:56:34 | 06/06/2018 1ST PLUMBING REVIEW**DENIED** | | | | | | 1) PROVIDE LEVEL OF ALTERATION AND TOTAL PERCENT OF | | | WORK AREA. FBC R-EXISTING 501.2 | | | | | | 2) PROVIDE THE SPECIFICATIONS/ INSTALLATION MANUALS | | | ALONG WITH FLOW CHARTS FOR THE TANKLESS WATER HEATERS. | | | FBC 107.2.1 | | | | | | 3) PROVIDE AN EXISTING FLOOR PLAN LAY OUT. FBC 107.2.1 | | | | | | 4) PROVIDE WALL DIMENSION FOR EACH ROOM TO SHOW THE | | | MINIMAL CLEARANCES FOR THE PLUMBING FIXTURES WILL | | | COMPLY. FBC R P2705.1 | | | | | | 5) IS THE COPPER PIPING SHOWN AS EXISTING IN THE LIVING | | | ROOM THE ONLY EXISTING WATER PIPING THAT WILL BE REUSED | | | IN THE NEW SYSTEM? FBC 107.2.1 | | | | | | 6) YOUR SANITARY ISOMETRIC IS SHOWING AS A WASTE & VENT | | | IN BATH #1 AND GUEST BATH. TOILETS AND GARBAGE | | | DISPOSALS ARE NOT PERMITTED TO DISCHARGE INTO THIS TYPE | | | OF SYSTEM PER FBC R P3111.1. PLEASE SHOW HOW YOU INTENT | | | TO VENT THESE TWO BATHROOM GROUPS. | | | | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES | | | DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] | | | |
|