| 2018-05-23 08:12:32 | REVIEW DONE UNDER 18050312 |
| 2018-05-22 15:25:51 | 05/21/2018 1ST GAS REVIEW**DENIED** WITH COMMENTS NOTE |
| | - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME |
| | AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED |
| | UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| | A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| | AHEAD OF EACH MP REGULATOR. 2017 FBC FUEL GAS SEC. |
| | 409.4, FBC FUEL GAS RES. SEC. G2420.4. |
| | 2. SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS |
| | APPLIANCES. WHERE IS COMBUSTION AIR PROVIDED BY THE |
| | BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM |
| | SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN |
| | ADDITION TO THE REQUIRED VENTILATION AIR? 2017 FGC |
| | SEC.304.9.3 OR 2017 FBC R G2407.9.3. COMBINED |
| | COMBUSTION AIR AND VENTILATION AIR SYSTEM. |
| | 3. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE FLAT LAYOUT PLAN PER 2017 FBC FUEL GAS SEC. |
| | 402.2 OR 2017 FBC FUEL GAS RES. SEC. G2413.2. |
| | 4. YOU SHOW A TANKLESS IN A GARAGE, PLEASE TELL ME HOW |
| | YOU ARE VENTING IT, SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE THE |
| | ROOF AND ANCHORING DETAILS OF THE GAS VENT(S) PER 2017 |
| | FBC FUEL GAS SECS. 502 THRU 505 OR 2017 FBC FUEL GAS |
| | RES. SECS. G2426 THRU G2429.1 |
| | 5. SUBMIT MANUFACTURER'S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT, |
| | GENERATOR, TANKLESS WATER HEATER, TO VERIFY COMPLIANCE |
| | WITH 2017 FBC FUEL GAS SEC.305.1 OR 2017 FBC FUEL GAS |
| | RES. SEC. G2408.1. |
| | 6. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| | SHALL BE ONSITE AT THE TIME OF INSPECTION 2017 FBC FUEL |
| | GAS SEC. 402.2 AND 301.3 OR 2017 FBC FUEL GAS RES. SEC. |
| | G2413.2 AND G2404.3. |
| | 7. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| | BTU LOAD ON THE SYSTEM ON EACH SHEET. REFER TO THE 2017 |
| | FBC-FUEL GAS SECS.401.8, 402.2, AND TABLES 402.4 (1) |
| | THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2413.4 |
| | AND TABLES G2413.4 (1 ) THROUGH G2413.4 (21). |
| | 8. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| | USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| | THE GAS CODE OR ANOTHER STANDARD THAT WAS USED IN THE |
| | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC FUEL |
| | GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4 |
| | (1) THRU 402.4 (37) OR 2017 FBC FUEL GAS RES. SEC. |
| | G2412.4, G2412.8, G2413.1, G2413.2, & G2413.3. |
| | 9. NEED SPEC ON TANKLESS TO VERIFY LOCATION SO PLEASE |
| | SUBMIT TWO COPIES OF THE TABLE FOR INSTALLATION |
| | CLEARANCES FROM THE MANUFACTURES INSTALLATION MANUAL. |
| | THE MANUAL REQUIRES A CLEARANCE OF EITHER 4 FEET OR 12 |
| | INCHES FROM ANY OPERABLE WINDOWS OR DOORS. SHOW THE |
| | LOCATION OF ALL OPERABLE WINDOWS AND DOORS ON THE PLAN |
| | AND THE DISTANCE OF THE TANKLESS WATER HEATER FROM |
| | EACH. WPB AMENDMENTS TO THE FBC SEC. 107.2.1. |
| | INFORMATION ON CONSTRUCTION DOCUMENTS |
| | 10. THE MANUFACTURER'S SPECIFICATIONS FOR THE GENERATOR |
| | ARE REQUIRED AND SHALL BE ONSITE FOR FINAL GAS |
| | INSPECTION. THE GENERATOR SHALL BE LISTED AND APPROVED. |
| | NFPA 58 SEC. 5.20.1. THE GENERATOR SHALL MEET THE |
| | REQUIREMENTS OF UL 2200. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | LUIS A. CRESPO |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |