Plan Review Notes
Plan Review Notes For Permit 18050282
Permit Number 18050282
Review Stop M
Sequence Number 1
Notes
Date Text
2018-05-21 13:09:291ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18050282
 5/21/18
  
 CODES IN EFFECT:
 FBC BC- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC MC- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RE- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC-SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUBMITTED PLANS FROM DME BREWING SOLUTIONS ARE
 SCHEMATIC THAT WILL REQUIRE MODIFICATIONS TO DEPICT THE
 ACTUAL FIELD INSTALLATION.THE DRAWINGS WILL ALSO
 REQUIRE SHOP DRAWING APPROVALS STAMPS BY THE MEP
 ENGINEER OF RECORD (PLEASE NOTE THAT DME BREWING
 SOLUTIONS IS A CANADIAN COMPANY WITH CANADIAN ENGINEERS
 THAT ARE NOT LICENSED TO DESIGN IN THE STATE OF
 FLORIDA).
  
 PLEASE NOTE THAT THE MAIN PERMIT FOR THE PROJECT
 (#17010884) WAS APPROVED BY REQUEST WITH A LIST OF
 DEFERRED SUBMITTALS THAT MUST BE ADDRESSED UNDER THIS
 SUBMITTAL APPLICATION, OR UNDER A SEPARATE SUBMITTAL
 APPLICATION. PLEASE SEE THE LIST ON SHEET CVR OF THE
 PERMITTED PLANS, AND ALSO PRINTED BELOW.
  
 5) PROVIDE AN EQUIPMENT SCHEDULE FOR THE BOILER, BOILER
 VENT PIPE, AND SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 EACH. PROVIDE A DIMENSIONED ELEVATION VIEW THAT
 INDICATES THE TOTAL VENT RUN FROM THE OUTLET OF THE
 BOILER TO THE TERMINATION CAP ABOVE THE ROOF. INDICATE
 HOW THE VENT WILL BE SUPPORTED AND ANCHORED TO THE ROOF
 STRUCTURE.
  
 6) PROVIDE STEAM PIPING DRAWINGS THAT SHOW THE PIPING
 RUNS, TYPES AND SIZES OF PIPE AND PIPE INSULATION.
  
 7) M2.1: PROVIDE A COMBUSTION AIR CALCULATION FOR THE
 BOILER PER SECTION 304 FBC-14 FUEL GAS. IT APPEARS BY
 THE DRAWING THAT THE ONE-PERMANENT-OPENING METHOD IS
 BEING PROVIDED. PLEASE SEE SECTION 304.6.2 AND RELOCATE
 THE OPENING OF THE AIR INTAKE TO A LOCATION WITHIN 12
 INCHES OF THE TOP OF THE ENCLOSURE.
  
 8) PROVIDE AN EQUIPMENT PLAN AND SCHEDULES FOR THE
 BREWERY TANKS AND KETTLES. LABEL EACH PIECE OF
 EQUIPMENT AND SHOW THE REQUIRED WORKING CLEARANCES.
 PLEASE NOTE COMPLIANCE WITH SECTION 1003.1 MAY BE
 REQUIRED FOR THE EQUIPMENT.
  
 9) PROVIDE AN EQUIPMENT SCHEDULE FOR THE CHILLER, AND
 CHILLED WATER PIPING PLANS THAT SHOW PIPING RUNS, TYPES
 AND SIZES OF PIPES AND PIPE INSULATIONS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719