| 2018-05-21 13:09:29 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18050282 |
| | 5/21/18 |
| | |
| | CODES IN EFFECT: |
| | FBC BC- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC MC- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC RE- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC-SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE SUBMITTED PLANS FROM DME BREWING SOLUTIONS ARE |
| | SCHEMATIC THAT WILL REQUIRE MODIFICATIONS TO DEPICT THE |
| | ACTUAL FIELD INSTALLATION.THE DRAWINGS WILL ALSO |
| | REQUIRE SHOP DRAWING APPROVALS STAMPS BY THE MEP |
| | ENGINEER OF RECORD (PLEASE NOTE THAT DME BREWING |
| | SOLUTIONS IS A CANADIAN COMPANY WITH CANADIAN ENGINEERS |
| | THAT ARE NOT LICENSED TO DESIGN IN THE STATE OF |
| | FLORIDA). |
| | |
| | PLEASE NOTE THAT THE MAIN PERMIT FOR THE PROJECT |
| | (#17010884) WAS APPROVED BY REQUEST WITH A LIST OF |
| | DEFERRED SUBMITTALS THAT MUST BE ADDRESSED UNDER THIS |
| | SUBMITTAL APPLICATION, OR UNDER A SEPARATE SUBMITTAL |
| | APPLICATION. PLEASE SEE THE LIST ON SHEET CVR OF THE |
| | PERMITTED PLANS, AND ALSO PRINTED BELOW. |
| | |
| | 5) PROVIDE AN EQUIPMENT SCHEDULE FOR THE BOILER, BOILER |
| | VENT PIPE, AND SUBMIT MANUFACTURER'S SPECIFICATIONS FOR |
| | EACH. PROVIDE A DIMENSIONED ELEVATION VIEW THAT |
| | INDICATES THE TOTAL VENT RUN FROM THE OUTLET OF THE |
| | BOILER TO THE TERMINATION CAP ABOVE THE ROOF. INDICATE |
| | HOW THE VENT WILL BE SUPPORTED AND ANCHORED TO THE ROOF |
| | STRUCTURE. |
| | |
| | 6) PROVIDE STEAM PIPING DRAWINGS THAT SHOW THE PIPING |
| | RUNS, TYPES AND SIZES OF PIPE AND PIPE INSULATION. |
| | |
| | 7) M2.1: PROVIDE A COMBUSTION AIR CALCULATION FOR THE |
| | BOILER PER SECTION 304 FBC-14 FUEL GAS. IT APPEARS BY |
| | THE DRAWING THAT THE ONE-PERMANENT-OPENING METHOD IS |
| | BEING PROVIDED. PLEASE SEE SECTION 304.6.2 AND RELOCATE |
| | THE OPENING OF THE AIR INTAKE TO A LOCATION WITHIN 12 |
| | INCHES OF THE TOP OF THE ENCLOSURE. |
| | |
| | 8) PROVIDE AN EQUIPMENT PLAN AND SCHEDULES FOR THE |
| | BREWERY TANKS AND KETTLES. LABEL EACH PIECE OF |
| | EQUIPMENT AND SHOW THE REQUIRED WORKING CLEARANCES. |
| | PLEASE NOTE COMPLIANCE WITH SECTION 1003.1 MAY BE |
| | REQUIRED FOR THE EQUIPMENT. |
| | |
| | 9) PROVIDE AN EQUIPMENT SCHEDULE FOR THE CHILLER, AND |
| | CHILLED WATER PIPING PLANS THAT SHOW PIPING RUNS, TYPES |
| | AND SIZES OF PIPES AND PIPE INSULATIONS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |