| Date |
Text |
| 2019-01-14 10:10:07 | UPON ADDRESS ASSIGNMENT, PLEASE UPLOAD COVER SHEET WITH |
| | NEW ADDRESS ON IT. |
| | |
| | COMMENT BY: |
| | DYLAN BATTLES |
| | 561-805-6718 |
| | [email protected] |
| | |
| | THE CITY OF WEST PALM BEACH |
| | BUILDING PLANS EXAMINER PX4191 |
| | COMMERCIAL BUILDING INSPECTOR BN7557 |
| | |
| 2018-12-13 13:24:56 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18050277 |
| | |
| | 1ST REVIEW |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | 2ND REVIEW: DECEMBER 12, 2018 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER I |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC ENERGY = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. OK |
| | |
| | 2 A1.0.04, HOW OCCPUANT LOAD OF 106 WAS DETERMINED IS |
| | NOT CLEAR. |
| | 2ND REVIEW: |
| | A) 2-2 SHEET A-0.0.02 BUILDING OCCUPANY TABLE DOESN?T |
| | MATCH OCCUPANT LOAD TABLE 1004.1.2. |
| | B) REQUIRED FIXTURE TABLE STATES A-3 OCCUPANCY, BUT IT |
| | SHOULD BE A-2. PLEASE ADJUST TO MATCH BUILDING CODE |
| | DATA. |
| | C) OCCUPANCY USED FOR REQUIRED FIXTURES SHOULD MATCH |
| | THE BUILDING OCCUPANCY CURRENTLY IT SAY 166 PERSONS FOR |
| | PLUMBING COUNT AND 106 FOR BUILDING OCCUPANCY. |
| | D) THE AMOUNT OF FIXTURES PROVIDED DOESN?T MATCH WHAT |
| | SHOWS IN PLAN VIEW ON SHEET A-1.0.05 AND PLUMBING |
| | SHEETS. |
| | PLEASE MATCH NUMBERS OF FIXTURE PROVIDED. |
| | E) REVIEW BUILDING OCCUPANCY AND USE FUNCTIONS FROM |
| | TABLE 1004.1.2 TO DETERMINE THE OCCUPANT LOAD [FBC |
| | 1004.6]MULTIPLE OCCUPANCIES |
| | EXAMPLE: |
| | A) 200 GROSS - KITCHENS COMMERCIAL I SEE THE INTERIOR |
| | COMMERCIAL KITCHEN AS APPROX. 400 SQ. PLUS THE OUTSIDE |
| | SERVING CAN BE INCLUDED. |
| | B) 300 GROSS ? STORAGE. THE SECTION BEHIND THE KITCHEN |
| | IS ABOUT 1574 SQ. FT |
| | |
| | C) 15 GROSS ? UNCONCENTRATED TABLES AND CHAIRS. THE |
| | OUTSIDE EATING CAN BE JUST THE AREA FROM BARS EDGE TO |
| | ROOFS EDGE. |
| | PLEASE UPDATE SO AREAS ARE CLEAR |
| | SQ. FOOTAGE UNDER AIR, SQ. FOOTAGE FOR OUTDOOR EATING |
| | AND TOTAL SQ. FOOTAGE. |
| | |
| | 3. OK |
| | |
| | 4. OK |
| | |
| | 5. OK |
| | |
| | 6. OK |
| | |
| | NEW COMMENTS: |
| | 7. REMOVE SHEET AGA A-1.0.0.01 SITE PLAN SINCE SHEET |
| | AGA A.0.0.05 IS THE APPROVED SITE PLAN. SHEETS AGA |
| | A1.0.02 AND AGA A1.0.03 MAY NOT BE NEEDED IN THE SET |
| | EITHER. |
| | |
| | 8. SHEET A-1.0.04 INFORMATION ON SHEET IS NOT SHOWING |
| | UP. PLEASE RE-LOAD THE SHEET WITH INTENDED CONTENT. |
| | |
| | 9. [FBC ENERGY C401.2]APPLICATION. |
| | COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF THE |
| | FOLLOWING: |
| | 1.THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1, EXCLUDING |
| | SECTION 9.4.1.1(G) OF THE STANDARD. |
| | 2.THE REQUIREMENTS OF SECTIONS C402 THROUGH C405. IN |
| | ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY WITH |
| | SECTION C406 AND TENANT SPACES SHALL COMPLY WITH |
| | SECTION C406.1.1. |
| | 3.THE REQUIREMENTS OF SECTIONS C402.5, C403.2, C404, |
| | C405.2, C405.3, C405.5, C405.6 AND C407. THE BUILDING |
| | ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 PERCENT |
| | OF THE STANDARD REFERENCE DESIGN BUILDING. |
| | NO ENERGY CALCULATIONS WERE FOUND IN SUPPORTING |
| | DOCUMENTS. |
| | PLEASE UPLOAD THE ENERGY CALCULATIONS (LOAD |
| | CALCULATIONS WERE PROVIDED) |
| | |
| | 10. SOME WALLTYPES ON FLOOR PLAN A-1.0.05 DON?T MATCH |
| | WITH WALL TYPES LISTED ON A-6.0.00 |
| | VERIFY ALL WALL TYPES TO MATCH |
| | |
| | NOTE: |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |
| | |
| | |
| | |