| 2018-06-11 12:01:18 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18050277 |
| | 6/11/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SEPARATE PERMITS ARE REQUIRED FOR THE COMMERCIAL |
| | KITCHEN HOOD, THE FIRE SUPRESSION SYSTEM, AND THE |
| | WALKIN FOOD STORAGE AND KEG COOLERS. PLEASE PLACE |
| | ADVISORY NOTES ON THE PLANS. |
| | |
| | 2) THE PROPOSED BUILDING SHALL BE IN COMPLIANCE WITH |
| | THE FBC EC. REFER TO SECTIONS C101.2 -SCOPE AND C401.2 |
| | APPLICATION (COMPLIANCE PATHS). PROVIDE A COMPLIANCE |
| | SUBMITTAL C101.5.1- COMPLIANCE MATERIALS, |
| | |
| | 2) SHEET M-1.3.01: PROVIDE EXHAUST VENTILATION |
| | CALCULATIONS FOR THE TOILET ROOMS, AND THE POOL |
| | EQUIPMENT AND CHEMICAL STORAGE ROOMS- TABLE 403.3.1 AND |
| | SECTION 510.2. FBC M |
| | |
| | 3) M-1.3.01, POOL EQP/STORAGE ROOM: A) INDICATE HOW |
| | MAKEUP AIR IS BEING PROVIDED TO THE ROOM- SECTION |
| | 510.6.5 FBC M B) CLARIFY HOW THE SYSTEM WILL OPERATE- |
| | CONTINUOUSLY OR INTERMITTENTLY. C) INDICATE THE TYPE OF |
| | EXHAUST DUCTWORK TO BE INSTALLED- SECTION 510.9. D) THE |
| | EXHAUST OUTLET APPEARS TO BE WITHIN 10' OF THE DOORS TO |
| | THE ROOM AND NOT IN COMPLIANCE WITH SECTION 501.3.1(2) |
| | FBC M. SHOW ALL REQUIRED CLEARANCE DISTANCE |
| | MEASUREMENTS ON THE PLAN. E) SUBMIT SPECIFICATIONS FOR |
| | THE CHEMICAL STORAGE TANKS AND EMBOLDEN THE PRINT ON |
| | THE TANK SYSMBOLS TO CLEARLY SHOW THE CHEMICAL NAME AND |
| | GALLON CONTENT- TABLE 414.2.5(1) FBC B. |
| | |
| | 4) M-0.0.01: PROVIDE AIR BALANCE CALCULATIONS FOR THE |
| | KITCHEN- SECTION 508.1.2 FBC M |
| | |
| | 5) M-1.3.01: PROVIDE A DUCT SMOKE DETECTOR ON THE |
| | SUPPLY TRUNK OF AC-1- SECTION 606.2.1 |
| | |
| | 6) M-1.3.01: PROVIDE WIND LOAD ENGINEERING FOR |
| | INSTALLATION OF CU-1 & CU-2- SECTION 301.15 FBC M. |
| | |
| | 7) K-1.4: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL |
| | GAS-FIRED COOKING EQUIPMENT- SECTION 623.1 FBC FG. |
| | |
| | 8) M-0.0.01: PROVIDE COMBUSTION AIR CALCULATIONS FOR |
| | THE GAS-FIRED COOKING APPLIANCES- SECTION 304 FBC FG. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |