| 2018-05-22 13:23:51 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET A 0.0.02 - THERE IS A NOTE, UNDER BUIOLDING |
| | CODE DATA, INDICATING "TYPE VB NONSPRINKLERED" YET |
| | THERE A FIRE PROTECTION DOCUMENTS SHOWING FIRE |
| | SPRINKLERS. |
| | |
| | PLEASE CORRECT OR JUSTIFY. |
| | |
| | |
| | |
| | 2) SHEET A 0.0.02 - UNDER "PROJECTS COMPONENTS, |
| | BUILDING OCCUPANCY" TABLE THERE ARE NO FIGURES ENTERED |
| | INTO THE COLUMNS LABLED "FACTOR OR PERSONS". |
| | |
| | |
| | PLEASE CORRECT |
| | |
| | |
| | |
| | 3) SHEET FP 0.0.00 - UNDER THE SECTION "FIRE PROTECTION |
| | FLOW TEST DATA" THERE ARE NO FIGURES ENTERED INTO AREAS |
| | INDICATED. THESE FIGURES ARE REQUIRED TO PROVIDE |
| | ADAQUATE WATER SUPPLY AND SYSTEM DEMANDS. |
| | |
| | PLEASE CORRECT. |
| | |
| | |
| | |
| | 4) SHEET FP 0.0.00 - UNDER THE SECTION " DESIGN |
| | CRITERIA" STORAGE, MECH/ELECT. ROOMS, ORDINARY HAZARD |
| | GRUOP 1 IS INDICATED. HOWEVER, ON SHEET FP 1.3.01 THERE |
| | ARE NO HEASD INDICATED IN THE ELECTRICAL ROOM. |
| | |
| | PER NFPA 13 |
| | |
| | 8.15.11 ELECTRICAL EQUIPMENT. |
| | 8.15.11.1 UNLESS THE REQUIREMENTS OF 8.15.11.3 ARE MET, |
| | SPRINKLER |
| | PROTECTION SHALL BE REQUIRED IN ELECTRICAL EQUIPMENT |
| | ROOMS. |
| | 8.15.11.2 HOODS OR SHIELDS INSTALLED TO PROTECT |
| | IMPORTANT |
| | ELECTRICAL EQUIPMENT FROM SPRINKLER DISCHARGE SHALL BE |
| | NONCOMBUSTIBLE. |
| | 8.15.11.3 SPRINKLERS SHALL NOT BE REQUIRED IN |
| | ELECTRICAL EQUIPMENT |
| | ROOMS WHERE ALL OF THE FOLLOWING CONDITIONS ARE MET: |
| | (1) THE ROOM IS DEDICATED TO ELECTRICAL EQUIPMENT ONLY. |
| | (2) ONLY DRY-TYPE ELECTRICAL EQUIPMENT IS USED. |
| | (3) EQUIPMENT IS INSTALLED IN A 2-HOUR FIRE-RATED |
| | ENCLOSURE |
| | INCLUDING PROTECTION FOR PENETRATIONS. |
| | (4) NO COMBUSTIBLE STORAGE IS PERMITTED TO BE STORED IN |
| | THE |
| | ROOM. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY. |
| | |
| | |
| | |
| | 5) SHEET 1.3.01 - THERE APPEARS TO BE NO SPRINKLER HEAD |
| | COVERAGE IN THE FRONT PORCH BAR AREA. |
| | |
| | PER NFPA 13 |
| | |
| | 8.15.1.2.18 SOFFITS, EAVES, OVERHANGS, AND DECORATIVE |
| | FRAME |
| | ELEMENTS. SPRINKLERS SHALL BE PERMITTED TO BE OMITTED |
| | FROM |
| | WITHIN COMBUSTIBLE SOFFITS, EAVES, OVERHANGS, AND |
| | DECORATIVE |
| | FRAME ELEMENTS THAT ARE CONSTRUCTED IN ACCORDANCE WITH |
| | 8.15.1.2.18.1 THROUGH 8.15.1.2.18.4. |
| | 8.15.1.2.18.1 COMBUSTIBLE SOFFITS, EAVES, OVERHANGS, |
| | AND DECORATIVE |
| | FRAME ELEMENTS SHALL NOT EXCEED 4 FT 0 IN. (1.2 M) IN |
| | WIDTH. |
| | 8.15.1.2.18.2 COMBUSTIBLE SOFFITS, EAVES, OVERHANGS, |
| | AND DECORATIVE |
| | FRAME ELEMENTS SHALL BE DRAFTSTOPPED, WITH A MATERIAL |
| | EQUIVALENT TO THAT OF THE SOFFIT, INTO VOLUMES NOT |
| | EXCEEDING 160 FT3 |
| | (4.5 M3). |
| | 8.15.1.2.18.3 COMBUSTIBLE SOFFITS, EAVES, OVERHANGS, |
| | AND DECORATIVE |
| | FRAME ELEMENTS SHALL BE SEPARATED FROM THE INTERIOR OF |
| | THE BUILDING BY WALLS OR ROOFS OF NONCOMBUSTIBLE OR |
| | LIMITEDCOMBUSTIBLE |
| | CONSTRUCTION. |
| | 8.15.1.2.18.4 COMBUSTIBLE SOFFITS, EAVES, OVERHANGS, |
| | AND DECORATIVE |
| | FRAME ELEMENTS SHALL HAVE NO OPENINGS OR UNPROTECTED |
| | PENETRATIONS DIRECTLY INTO THE BUILDING. |
| | |
| | PLEASE REVIEW AND PROVIDE HEAD COVERAGE OR JUSTIFY WITH |
| | SPECIFIC FIRE CODE DETAILS. |
| | |
| | |
| | |
| | 6) THERE ARE NO INDICATIONS OF HOW THIS FIRE SPRINKLER |
| | SYSTEM WILL BE MONITORED AND WHERE THE FACP WILL BE |
| | LOCATED. |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS. |
| | |
| | |
| | |
| | 7) THERE ARE NO INDICATIONS OF THE INSTALL OF THE |
| | KITCHEN HOOD AND/OR FIRE SUPPRESSION SYSTEM. |
| | |
| | THE KITCHEN HOOD AND FIRE SUPPRESSION SHALL BE |
| | SUBMITTED UNDER SEPARATE SHOP DRAWINGS EACH IN |
| | COMPLIANCE WITH NFPA 96 & 2001. |
| | |
| | PLEASE PROVIDE AND APPLICABLE NOTE OF ACKNOWLEDGMENT |
| | AND COMPLIANCE. |
| | |
| | |
| | |
| | 8) THERE IS A CHLORINE STORAGE ROOM THAT DOES APPEAR TO |
| | BE PROTECTED PER THE REQUIREMENT. |
| | |
| | PER NFPA 101, CHAPTER 12 NEW ASSEMBLY OCCUPANCIES |
| | |
| | 12.3.2 PROTECTION FROM HAZARDS. |
| | 12.3.2.1 SERVICE EQUIPMENT, HAZARDOUS OPERATIONS OR |
| | PROCESSES, AND STORAGE FACILITIES. |
| | 12.3.2.1.2 ROOMS OR SPACES FOR THE STORAGE, PROCESSING, |
| | OR USE OF |
| | MATERIALS SPECIFIED IN 12.3.2.1.2(1) THROUGH (3) SHALL |
| | BE PROTECTED |
| | IN ACCORDANCE WITH ONE OF THE FOLLOWING: |
| | (1) SEPARATION FROM THE REMAINDER OF THE BUILDING BY |
| | FIRE BARRIERS |
| | HAVING A MINIMUM 1-HOUR FIRE RESISTANCE RATING OR |
| | PROTECTION |
| | OF SUCH ROOMS BY AUTOMATIC EXTINGUISHING SYSTEMS AS |
| | SPECIFIED IN SECTION 8.7 IN THE FOLLOWING AREAS: |
| | (C) ROOMS OR SPACES USED FOR THE STORAGE OF HAZARDOUS |
| | MATERIALS OR FLAMMABLE OR COMBUSTIBLE LIQUIDS IN |
| | QUANTITIES DEEMED HAZARDOUS BY RECOGNIZED STANDARDS |
| | |
| | PLEASE REVIEW AND CORRECT WITH SPECIFIC DETAILS. |
| | |
| | |
| | 9) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 10) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |