| Notes |
| Date |
Text |
| 2018-05-10 07:35:05 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC B 1609, ENGINEERING INDICATES OPENING 1 AS ZONE | | | 4, BUT THE FLOOR PLAN SHOWS THIS AS ZONE 5. PLEASE | | | CORRELATE, AND IF IN ZONE 4, PROVIDE THE DIMENSION OF | | | OPENING FROM THE CORNERS, AS WELL AS ZONE 5 DIMENSION. | | | PRODUCT PROPOSED APPEARS COMPLIANT FOR ZONE 5, BUT NOT | | | ENTIRELY CLEAR AS ZONE 5 PRESSURES WERE NOT PROVIDED. | | | | | | 2. SHEET 4, THANK YOU FOR INDICATING FASTENING OPTIONS | | | PROPOSED. HOWEVER, THE POSITIVE DESIGN PRESSURES WERE | | | CROSSED OFF; THEY APPEAR TO COMPLY, NOT CLEAR WHY THEY | | | WERE CROSSED OFF, PLEASE PROVIDE EXPLANATION. | | | | | | | | | | | | |
|