2018-05-07 16:55:49FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E-1
  
 RISER FOR SIGNAGE DOES NOT REFLECT RISER THAT IS ON
 PAGE E-2
  
 PAGE E-2
  
 CONDUIT FROM METER TO PANEL SHOWS 1", THIS CONDUIT IS
 TOO SMALLL.
  
 PLANS IDICATE THAT YOU CHANGED AND ADDED ONE PANEL TO A
 MORE EFFICIENT PANEL. COST OF THE WORK
 COULD NOT HAVE STAYED THE SAME. PLUS YOU HAD TO CHANGE
 THE WIRE TO THE PANEL ACCORDING TO THE RISER.
  
 APPLICATION INDICATED THE ZERO VALUE WAS ADDED TO THE
 JOB.