| Plan Review Notes For Permit 18050259 |
| Permit Number |
18050259 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-05-07 16:55:49 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PAGE E-1 | | | | | | RISER FOR SIGNAGE DOES NOT REFLECT RISER THAT IS ON | | | PAGE E-2 | | | | | | PAGE E-2 | | | | | | CONDUIT FROM METER TO PANEL SHOWS 1", THIS CONDUIT IS | | | TOO SMALLL. | | | | | | PLANS IDICATE THAT YOU CHANGED AND ADDED ONE PANEL TO A | | | MORE EFFICIENT PANEL. COST OF THE WORK | | | COULD NOT HAVE STAYED THE SAME. PLUS YOU HAD TO CHANGE | | | THE WIRE TO THE PANEL ACCORDING TO THE RISER. | | | | | | APPLICATION INDICATED THE ZERO VALUE WAS ADDED TO THE | | | JOB. |
|