| Plan Review Notes For Permit 18050255 |
| Permit Number |
18050255 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-08-14 10:25:37 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | COMMENT #1 PANEL "G" NOT DONE NO AIC RATING SHOWN | | | | | | COMMENT #2 NO CALCLUATION SHOWN ON DRAWINGS FAULT | | | CURRENT CALC NO SHOWN | | | | | | COMMENT #9 NO SIZE ON PULL BOX | | | | | | COMMENT #10 NO GROUNDING DETAIL SHOWN | | | | | | COMMENT #11 NO CONTRACT SUBMITTED, PERMIT VALUE WILL BE | | | BASED ON $75,000. |
|