2018-05-10 11:26:57CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9
 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 3. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 4. PROVIDE RATED VOLTAGE OF SYSTEM ON PLAN. WPB FBC
 107.2.1; NEC 110.4
 5. PROVIDE LOAD CALCULATION FOR SERVICE TO CONFIRM
 CAPACITY OF GENERATOR IS ADEQUATE. NEC 215.2, 220,
 408.30, 702.4
 6. PROVIDE SIGNS FOR GENERATOR IN COMPLIANCE WITH NEC
 702.6.
 7. PROVIDE EQUIPMENT GROUNDING CONDUCTOR IN CONDUITS
 FROM TRANSFER SWITCH TO INTERIOR PANEL. INCLUDE
 DIRECTION TO SEPARATE GROUNDS AND NEUTRALS AT THE
 ORIGINAL MAIN, WHICH WILL NOW BE A SUB-PANEL. NEC
 250.122
 8. PROVIDE PANEL SCHEDULE FOR ANY NEW CIRCUITS THAT
 WILL BE ADDED FOR GENERATOR LIGHTING, BLOCK HEATER,
 ETC. WPB FBC 107.2.1; NEC 215.2, 408.4
 9. PULL BOX MUST BE SIZED PER NEC 314.28(A)(2). PROVIDE
 CORRECTION.
 10. PROVIDE DETAIL OF GROUNDING ELECTRODE SYSTEM AND
 ATTACHMENT TO MAIN SERVICE, WHICH WILL NOW BE THE
 TRANSFER SWITCH. NEC 250.50, 250.53, 250.64
 11. VALUE SPECIFIED ON PERMIT APPLICATION APPEARS LOW.
 PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE OF
 WORK, TO INCLUDE ALL MATERIALS AND LABOR. FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  