| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL. |
| | NEC 110.3, 110.9 |
| | 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 |
| | 3. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| | 4. PROVIDE RATED VOLTAGE OF SYSTEM ON PLAN. WPB FBC |
| | 107.2.1; NEC 110.4 |
| | 5. PROVIDE LOAD CALCULATION FOR SERVICE TO CONFIRM |
| | CAPACITY OF GENERATOR IS ADEQUATE. NEC 215.2, 220, |
| | 408.30, 702.4 |
| | 6. PROVIDE SIGNS FOR GENERATOR IN COMPLIANCE WITH NEC |
| | 702.6. |
| | 7. PROVIDE EQUIPMENT GROUNDING CONDUCTOR IN CONDUITS |
| | FROM TRANSFER SWITCH TO INTERIOR PANEL. INCLUDE |
| | DIRECTION TO SEPARATE GROUNDS AND NEUTRALS AT THE |
| | ORIGINAL MAIN, WHICH WILL NOW BE A SUB-PANEL. NEC |
| | 250.122 |
| | 8. PROVIDE PANEL SCHEDULE FOR ANY NEW CIRCUITS THAT |
| | WILL BE ADDED FOR GENERATOR LIGHTING, BLOCK HEATER, |
| | ETC. WPB FBC 107.2.1; NEC 215.2, 408.4 |
| | 9. PULL BOX MUST BE SIZED PER NEC 314.28(A)(2). PROVIDE |
| | CORRECTION. |
| | 10. PROVIDE DETAIL OF GROUNDING ELECTRODE SYSTEM AND |
| | ATTACHMENT TO MAIN SERVICE, WHICH WILL NOW BE THE |
| | TRANSFER SWITCH. NEC 250.50, 250.53, 250.64 |
| | 11. VALUE SPECIFIED ON PERMIT APPLICATION APPEARS LOW. |
| | PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE OF |
| | WORK, TO INCLUDE ALL MATERIALS AND LABOR. FBC 109.3 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |