| Plan Review Notes For Permit 18050250 |
| Permit Number |
18050250 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-05-12 10:16:41 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER, PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PROVIDE INSTALLATION SCHEDULE FOR EACH OPENING. | | | 2. NOTE THERE WILL BE A MINIMUM 0.90 FACTOR APPLIED FOR | | | EDGE DISTANCE FOR TAPCONS AND/OR TAPCONS WITH ADVANCED | | | THREADFORM TECHNOLOGY. SEE PG. 13 OF 20 OF PRODUCT | | | APPROVAL FL389-R9 OR FASTENER SPACING IN MASONRY TABLE, | | | PAGE 7 OF 7 OF PRODUCT APPROVAL FL16984-R2. | | | | | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE | | | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. | | | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY | | | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK | | | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, | | | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING | | | OFFICIAL. | | | | | | DUE TO THE DEFICIENCIES OF THIS PLAN, A COMPLETE AND | | | THOROUGH REVIEW CANNOT BE PERFORMED AT THIS TIME. UPON | | | RE-SUBMITTAL, ADDITIONAL COMMENTS MAY BE MADE. | | | | | | |
|