| Date |
Text |
| 2018-06-06 10:56:01 | 1ST REVIEW: FBC 2017 6TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. PLEASE PROVIDE THE DISTANCE BETWEEN THE GAS METER |
| | AND STEPDOWN REGULATOR 2PSI TO .5PSI SHOW DISTANCE AND |
| | SIZE ON RISER. PER 2017 FBC-FUEL GAS, SECS. 402.4.1, |
| | 402.4.2. |
| | |
| | 2. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / |
| | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| | FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017 |
| | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. |
| | |
| | 3. SHT. P2.1 THE NOTE FOR THE GAS REFERENCES NFPA 54 |
| | BUT THE TABLE LISTED IS OUT OF THE FBC FUEL GAS THIS |
| | PROJECT SHALL COMPLY WITH FBC FUEL GAS PLEASE CLARIFY. |
| | |
| | 4. SHT. P2.1 THE NOTE FOR THE GAS LISTS SYSTEM PRESSURE |
| | AT LESS THAN 2PSI WITH A .5PSI PRESSURE DROP IT ALSO |
| | LIST TABLE 402.4(5) WHICH IS A 2PSI SYSTEM PLEASE |
| | CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 5. SHOW ALL VALVES AND DRIP LEGS ON RISER. PER FBC FUEL |
| | GAS 408.4 , 409.1.1 AND WPB AMEND TO FBC 107.2.1 |
| | |
| | 6. SHT. P3.0 DETAIL #5 SHOWS AND SINGLE CONCENTRIC VENT |
| | DETAIL #10 IS SHOWING A TWO PIPE SYSTEM PLEASE CLARIFY. |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |