| Notes |
| Date |
Text |
| 2018-05-10 16:46:57 | 1ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL | | | REVISION #18050223 | | | MASTER PERMIT #17090214 | | | 5/10/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE GAS | | | COOKING APPLIANCE, THE EXHAUST HOOD AND THE EXHAUST | | | DUCT. | | | | | | 2) PROVIDE A DRAWING SHOWING THE HOOD AND EXHAUST DUCT | | | RUN FROM HOOD OUTLET TO ROOF TERMINATION. INCLUDE THE | | | LENGTH MEASUREMENT OF THE RUN. | | | | | | 3) REVISE THE GAS ISOMETRIC DRAWING TO INCLUDE THE NEW | | | APPLIANCE. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | | | | | | | |
|