2018-07-28 09:25:33ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 SAME VIOLATIONS AS LAST REVIEW.
  
 1. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND
 SIGNED/SEALED BY A DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
  
 2. PLAN IS BLURRY AND UNREADABLE. SUBMIT CLEAR COPIES
 OF PLANS. NOTES AND REVISION BUBBLES CANNOT BE READ ON
 SEVERAL PAGES OF ALL PLANS.
  
 3. PER FBC B1023.5 & 1023.6 (5TH EDITION 2014)
 PENETRATIONS IN THE STAIRWELLS ARE FORBIDDEN. PLEASE
 VERIFY RISER WILL NOT BE USING STAIRWELLS AS A RACEWAY.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTE
  