Plan Review Notes
Plan Review Notes For Permit 18050209
Permit Number 18050209
Review Stop E
Sequence Number 1
Notes
Date Text
2018-05-19 09:01:22ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND
 SIGNED/SEALED BY A DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
  
 2. PLAN IS BLURRY AND UNREADABLE. SUBMIT CLEAR COPIES
 OF PLANS.
  
 3. PER FBC B1023.5 & 1023.6 (5TH EDITION 2014)
 PENETRATIONS IN THE STAIRWELLS ARE FORBIDDEN. PLEASE
 VERIFY RISER WILL NOT BE USING STAIRWELLS AS A RACEWAY.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTE
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  
2018-05-16 08:09:515/16/18
  
 EOR TESTING REQUIRED AS OUTLINED IN NFPA 72 AND ALL
 RELATED STANDARDS IN ADDITION TO FD TESTING IN THE
 FIELD.
  
 SENT TO ELECTRICAL
  
 SLT 7805
2018-05-09 11:55:315/9/18 SENT TO FD JLEAHY