| Plan Review Notes For Permit 18050209 |
| Permit Number |
18050209 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-05-19 09:01:22 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND | | | SIGNED/SEALED BY A DESIGN PROFESSIONAL OR THE | | | ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS | | | 471.003(2)(H); 471.025; WPB FBC 107.1 | | | | | | 2. PLAN IS BLURRY AND UNREADABLE. SUBMIT CLEAR COPIES | | | OF PLANS. | | | | | | 3. PER FBC B1023.5 & 1023.6 (5TH EDITION 2014) | | | PENETRATIONS IN THE STAIRWELLS ARE FORBIDDEN. PLEASE | | | VERIFY RISER WILL NOT BE USING STAIRWELLS AS A RACEWAY. | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTE | | | | | | V/R, | | | | | | FRANK GIAQUINTO | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WPB | | | [email protected] | | | CELL: 561-657-1653 | | | | | 2018-05-16 08:09:51 | 5/16/18 | | | | | | EOR TESTING REQUIRED AS OUTLINED IN NFPA 72 AND ALL | | | RELATED STANDARDS IN ADDITION TO FD TESTING IN THE | | | FIELD. | | | | | | SENT TO ELECTRICAL | | | | | | SLT 7805 | | 2018-05-09 11:55:31 | 5/9/18 SENT TO FD JLEAHY |
|