| Plan Review Notes For Permit 18050196 |
| Permit Number |
18050196 |
|
| Review Stop |
Z |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-10-11 16:14:09 | FAILED | | | | | | 1) THANK YOU FOR PROVIDING THE HEIGHT OF THE GENERATOR | | | AND THE EXISTING WALL TO VERIFY THAT THE WALL HEIGHT | | | NEEDED TO BE INCREASED. | | | | | | 2) THE TWO FOOT INCREASE IN THE WALL HEIGHT REQUIRES A | | | MINOR PLANNED DEVELOPMENT AMENDMENT TO SHOW THE | | | INCREASED HEIGHT OF THE EXISTING WALL ON THE MASTER | | | SITE PLAN. | | | | | | 3) PLEASE NOTE THAT THE PLANS SEEM TO INDICATE THAT | | | ONLY THE WEST SIDE OF THE ENCLOSUREE WALL WILL BE | | | RAISED. IF ANY PART OF THE ENCLOSUR WALL IS INCREASED, | | | THE ENTIRE ENTIRE ENCLOSURE WALL NEEDS TO BE INCREASED | | | WITH THE SAME HEIGHT AND WALL CAP. | | | | | | 4) THE PLANS SEEM TO INDICATE THAT THE ENTIRE | | | GENERATOR, WITH TANK AND SLAB WILL BE 8 FEET 3 INCHES | | | IN HEIGHT. IF THIS IS THE CASE, IT MAY BE TO YOUR | | | BENEFIT TO REPLACE THE DECORATIVE CAP ON THE TOP OF THE | | | WALL WITH A HIGHER PROFILE CAP (4 INCHES TALLER) | | | INSTEAD OF ADDING TWO FEET OF WALL HEIGHT. AS LONG AS | | | THE TOTAL HEIGHT OF THE DECORATIVE CAP DOES NOT EXCEED | | | 9.6 INCHES (10% OF THE 8 FOOT WALL HEIGHT), YOU WOULD | | | NOT NEED TO SUBMIT THE MINOR AMENDMENT. YOU WOULD STILL | | | NEED TO PUT THE NEW DECORATIVE CAP AROUND THE ENTIRE | | | ENCLOSURE. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | | [email protected] |
|